1101 STEVENSON AVE (3)RECEIVED BY: S.A.
NOV 0 8 2018
PLANNING & DEVELOPMENT
CITY OF CLEARWATER
1101 STEVENSON AVE
BCP2018-03831 C
ELEV. CERT.
VORAS
Zoning: Low Medium Density
Atlas #: 260A
FEMA
NATIONAL FLOOD INSURANCE PROGRAM
ELEVATION CERTIFICATE
AND
INSTRUCTIONS
2015 EDITION
OMB No. 1660-0008
Expiration Date: November 30, 2018
U.S. DEPARTMENT OF HOMELAND SECURITY
Federal Emergency Management Agency
National Flood Insurance Program
ELEVATION CERTIFICATE AND INSTRUCTIONS
Paperwork Reduction Act Notice
Public reporting burden for this data collection is estimated to average 3.75 hours per response. The burden estimate includes the
time for reviewing instructions, searching existing data sources, gathering and maintaining the data needed, and completing and
submitting this form. You are not required to respond to this collection of information unless a valid OMB control number is
displayed on this form. Send comments regarding the accuracy of the burden estimate and any suggestions for reducing the
burden to: Information Collections Management, Department of Homeland Security, Federal Emergency Management Agency,
1800 South Bell Street, Arlington, VA 20598-3005, Paperwork Reduction Project (1660-0008). NOTE: Do not send your
completed form to this address.
Privacy Act Statement
Authority: Title 44 CFR § 61.7 and 61.8.
Principal Purpose(s): This information is being collected for the primary purpose of estimating the risk premium rates necessary
to provide flood insurance for new or substantially improved structures in designated Special Flood Hazard Areas.
Routine Use(s): The information on this form may be disclosed as generally permitted under 5 U.S.C. § 552a(b) of the Privacy Act
of 1974, as amended. This includes using this information as necessary and authorized by the routine uses published in DHS/
FEMA -003 — National Flood Insurance Program Files System or Records Notice 73 Fed. Reg. 77747 (December 19, 2008); DHS/
FEMA/NFIP/LOMA-1 — National Flood Insurance Program (NFIP) Letter of Map Amendment (LOMA) System of Records Notice 71
Fed. Reg. 7990 (February 15, 2006); and upon written request, written consent, by agreement, or as required by law.
Disclosure: The disclosure of information on this form is voluntary; however, failure to provide the information requested may
result in the inability to obtain flood insurance through the National Flood Insurance Program or the applicant may be subject to
higher premium rates for flood insurance. Information will only be released as permitted by law.
Purpose of the Elevation Certificate
The Elevation Certificate is an important administrative tool of the National Flood Insurance Program (NFIP). It is to be used to
provide elevation information necessary to ensure compliance with community floodplain management ordinances, to determine
the proper insurance premium rate, and to support a request for a Letter of Map Amendment (LOMA) or Letter of Map Revision
based on fill (LOMR-F).
The Elevation Certificate is required in order to properly rate Post -FIRM buildings, which are buildings constructed after publication
of the Flood Insurance Rate Map (FIRM), located in flood insurance Zones Al A30, AE, AH, A (with BFE), VE, V1 V30, V (with
BFE), AR, AR/A, AR/AE, AR/A1—A30, AR/AH, and AR/AO. The Elevation Certificate is not required for Pre -FIRM buildings unless
the building is being rated under the optional Post -FIRM flood insurance rules.
As part of the agreement for making flood insurance available in a community, the NFIP requires the community to adopt floodplain
management regulations that specify minimum requirements for reducing flood losses. One such requirement is for the community
to obtain the elevation of the lowest floor (including basement) of all new and substantially improved buildings, and maintain a
record of such information. The Elevation Certificate provides a way for a community to document compliance with the community's
floodplain management ordinance.
Use of this certificate does not provide a waiver of the flood insurance purchase requirement. Only a LOMA or LOMR-F from the
Federal Emergency Management Agency (FEMA) can amend the FIRM and remove the Federal mandate for a lending institution
to require the purchase of flood insurance. However, the lending institution has the option of requiring flood insurance even if a
LOMA/LOMR-F has been issued by FEMA. The Elevation Certificate may be used to support a LOMA or LOMR-F request. Lowest
floor and lowest adjacent grade elevations certified by a surveyor or engineer will be required if the certificate is used to support a
LOMA or LOMR-F request. A LOMA or LOMR-F request must be submitted with either a completed FEMA MT -EZ or MT -1
package, whichever is appropriate.
This certificate is used only to certify building elevations. A separate certificate is required for floodproofing. Under the NFIP, non-
residential buildings can be floodproofed up to or above the Base Flood Elevation (BFE). A floodproofed building is a building that
has been designed and constructed to be watertight (substantially impermeable to floodwaters) below the BFE. Floodproofing of
residential buildings is not permitted under the NFIP unless FEMA has granted the community an exception for residential
floodproofed basements. The community must adopt standards for design and construction of floodproofed basements before
FEMA will grant a basement exception. For both floodproofed non-residential buildings and residential floodproofed basements in
communities that have been granted an exception by FEMA, a floodproofing certificate is required.
Additional guidance can be found in FEMA Publication 467-1, Floodplain Management Bulletin: Elevation Certificate, available on
FEMA's website at https://www.fema.gov/media-library/assets/documents/3539?id=1727.
FEMA Form 086-0-33 (Revised 7/15) Replaces all previous editions. F-053
U.S. DEPARTMENT OF HOMELAND SECURITY
Federal Emergency Management Agency
National Flood Insurance Program
ELEVATION CERTIFICATE
Important: Follow the instructions on pages 1-9.
OMB No. 1660-0008
Expiration Date: November 30, 2018
Copy all pages of this Elevation Certificate and all attachments for (1) community official, (2) insurance agent/company, and (3) budding owner.
SECTION A — PROPERTY INFORMATION
FOR INSURANCE COMPANY USE
Al. Building Owner's Name
STEVEN AND MARIA VORAS
Policy Number:
A2. Budding Street Address (including Apt., Unit, Suite, and/or Bldg. No.) or P.O. Route and
Box No.
1101 STEVENSON AVE.
Company NAIC Number:
City State ZIP Code
CLEARWATER Florida 33755
A3. Property Description (Lot and Block Numbers, Tax Parcel Number, Legal Description, etc.)
PARCEL NUMBER 03-29-15-88110-004-0240
A4. Building Use (e.g.,
A5. Latitude/Longitude:
A6. Attach at least
A7. Building Diagram
A8. For a building
a) Square footage
b) Number of permanent
c) Total net area
d) Engineered
A9. For a building with
a) Square footage
b) Number of permanent
c) Total net area
d) Engineered
Residential, Non -Residential, Addition, Accessory, etc.)
Lat. N27.9877* Long. W082.7912*
RESIDENTIAL
Horizontal
Datum:
insurance.
above
❑ NAD 1927
adjacent grade
grade N/A
x NAD 1983
N/A
2 photographs
Number
with a crawlspace
of crawlspace
flood
of flood openings
flood openings?
an attached
of attached
flood
of flood openings
flood openings?
of the building if the
1B
Certificate is being used to obtain flood
N/A sq ft
or enclosure(s):
or enclosure(s)
openings in the crawlspace
in A8.b
or enclosure(s)
N/A sq in
within 1.0 foot
foot above adjacent
in
N/A sq ft
❑ Yes x No
garage:
garage
openings in the attached garage within 1.0
in A9.b N/A sq
❑ Yes x No
SECTION B — FLOOD INSURANCE RATE MAP (FIRM) INFORMATION
B1. NFIP Community Name & Community Number
125096 CITY OF CLEARWATER FLORIDA
B2. County Name
PINELLAS
B3. State
Florida
B4. Map/Panel
Number
12103C0106
B5. Suffix
H
B6. FIRM Index
Date
05-17-2005
B7. FIRM Panel
Effective/
Revised Date
05-17-2005
B8. Flood
Zone(s)
AE
B9. Base Flood E evation(s)
(Zone AO, use Base Flood Depth)
12'
B10. Indicate the source
❑ FIS Profile
B11. Indicate elevation
B12. Is the building
Designation
of the
Base Flood Elevation
❑ Community Determined
for BFE in Item B9:
Coastal Barrier Resources
❑
(BFE) data
❑ NGVD
System
CBRS
or base flood
❑ Other/Source:
depth entered in Item B9:
x FIRM
datum used
located in a
Date:
❑ Other/Source:
Protected
1929 x NAVD 1988
(CBRS) area or Otherwise
❑ OPA
Area (OPA)?
❑ Yes x No
FEMA Form 086-0-33 (7/15)
Replaces all previous editions.
Form Page 1 of 6
ELEVATION CERTIFICATE
OMB No. 1660-0008
Expiration Date: November 30, 2018
IMPORTANT: In these spaces, copy the corresponding information from Section A.
FOR INSURANCE COMPANY USE
Building Street Address (including Apt., Unit, Suite, and/or Bldg. No.) or P.O. Route and Box No.
1101 STEVENSON AVE.
Policy Number:
City State ZIP Code
CLEARWATER Florida 33755
Company NAIC Number
SECTION C — BUILDING ELEVATION INFORMATION (SURVEY REQUIRED)
❑ Finished Construction
AR/A1—A30, AR/AH, AR/AO.
Rico only, enter meters.
C1. Building elevations are based on: ❑ Construction Drawings* p Building Under Construction*
*A new Elevation Certificate will be required when construction of the building is complete.
C2. Elevations — Zones A1—A30, AE, AH, A (with BFE), VE, V1—V30, V (with BFE), AR, AR/A, AR/AE,
Complete Items C2.a—h below according to the building diagram specified in Item A7. In Puerto
Benchmark Utilized: NGS PID AG0303 Vertical Datum: NAVD 1988
Indicate elevation datum used for the elevations in items a) through h) below.
❑ NGVD 1929 x NAVD 1988 ❑ Other/Source:
Datum used for building elevations must be the same as that used for the BFE.
Check the measurement used.
a) Top of bottom floor (including basement, crawlspace, or enclosure floor) 13.30 ❑x feet ❑ meters
b) Top of the next higher floor N/A ❑ feet ❑ meters
c) Bottom of the lowest horizontal structural member (V Zones only) N/A ❑ feet ❑ meters
d) Attached garage (top of slab) N/A ❑ feet ❑ meters
e) Lowest elevation of machinery or equipment servicing the building
(Describe feet metersbe type of equipment and location in Comments) ❑ ❑
f) Lowest adjacent (finished) grade next to building (LAG) 7.80
x feet ❑ meters
g) Highest adjacent (finished) grade next to building (HAG) 12.65
x feet ❑ meters
h) Lowest adjacent grade at lowest elevation of deck or stairs, including
structural support
N/A ❑ feet • meters
SECTION D — SURVEYOR, ENGINEER, OR ARCHITECT CERTIFICATION
This certification is to be signed and sealed by a land surveyor, engineer, or architect authorized by
I certify that the information on this Certificate represents my best efforts to interpret the data available.
statement may be punishable by fine or imprisonment under 18 U.S. Code, Section 1001.
law to certify elevation information.
I understand that any false
❑ Check here if attachments.
Were latitude and longitude in Section A provided by a licensed land surveyor? x Yes ❑ No
Certifier's Name License Number
DENNIS V. MOYLAN LS6115
eC7)??,X
f i
k�C `,
g�.�` '
Here
Title
PROFESSIONAL SURVEYOR AND MAPPER(
Company Name
DENNIS MOYLAN PSM, INC
Address
5342 BIRCHWOOD RD
City State ZIP Code
SPRING HILL Florida 34608
Signature�% Date Telephone
i�•s• s:���" 09-21-2018 (352) 684-5450
Ext.
Copy all pages of this Elevation Certifica and all attachments for (1) community official, (2) insurance agent/company, and (3) building owner.
Comments (including type of equipment and location, per C2(e), if applicable)
C2 ELEVATION NGS DI2886. USING GPS TOPCON GR3 .
•
FEMA Form 086-0-33 (7/15)
Replaces all previous editions.
Form Page 2 of 6
ELEVATION CERTIFICATE
OMB No. 1660-0008
Expiration Date: November 30, 2018
IMPORTANT: In these spaces, copy the corresponding information from Section A.
FOR INSURANCE COMPANY USE
Building Street Address (including Apt., Unit, Suite, and/or Bldg. No.) or P.O. Route and Box No.
1101 STEVENSON AVE.
Policy Number:
City State ZIP Code
CLEARWATER Florida 33755
Company NAIC Number
SECTION E — BUILDING ELEVATION INFORMATION (SURVEY NOT REQUIRED)
FOR ZONE AO AND ZONE A (WITHOUT BFE)
For Zones AO and A (without BFE), complete Items E1—E5. If the Certificate is intended to support a
complete Sections A, B,and C. For Items E1—E4, use natural grade, if available. Check the measurement
enter meters.
El. Provide elevation information for the following and check the appropriate boxes to show whether
the highest adjacent grade (HAG) and the lowest adjacent grade (LAG).
a) Top of bottom floor (including basement,
crawlspace, or enclosure) is ❑ feet ❑ meters
LOMA or LOMR-F request,
used. In Puerto Rico only,
the elevation is above or below
❑ above or ❑ below the HAG.
❑ above or ❑ below the LAG.
9 (see pages 1-2 of Instructions),
❑ above or ❑ below the HAG.
b) Top of bottom floor (including basement,
crawlspace, or enclosure) is ❑ feet ❑ meters
E2. For Building Diagrams 6-9 with permanent flood openings provided in Section A Items 8 and/or
the next higher floor (elevation C2.b in
the diagrams) of the building is ❑ feet ❑ meters
E3. Attached garage (top of slab) is ❑ feet ❑ meters
❑ above or • below the HAG.
E4. Top of platform of machinery and/or equipment
servicing the building is ❑ feet ❑ meters
❑ above or ❑ below the HAG.
with the community's
certify this information in Section G.
E5. Zone AO only: If no flood depth number is available, is the top of the bottom floor elevated in accordance
floodplain management ordinance? ❑ Yes ❑ No ❑ Unknown. The local official must
SECTION F — PROPERTY OWNER (OR OWNER'S REPRESENTATIVE) CERTIFICATION
The property owner or owner's authorized representative who completes Sections A, B, and E for Zone A (without a FEMA -issued or
community -issued BFE) or Zone AO must sign here. The statements in Sections A, B, and E are correct to the best of my knowledge.
Property Owner or Owner's Authorized Representative's Name
Address City State ZIP Code
Signature Date Telephone
Comments
❑ Check here if attachments.
FEMA Form 086-0-33 (7/15)
Replaces all previous editions.
Form Page 3 of 6
ELEVATION CERTIFICATE
OMB No. 1660-0008
Expiration Date: November 30, 2018
IMPORTANT: In these spaces, copy the corresponding information from Section A.
FOR INSURANCE COMPANY USE
Building Street Address (including Apt., Unit, Suite, and/or Bldg. No.) or P.O. Route and Box No.
1101 STEVENSON AVE.
Policy Number:
City State ZIP Code
CLEARWATER Florida 33755
Company NAIC Number
SECTION G — COMMUNITY INFORMATION (OPTIONAL)
The local official who is authorized by law or ordinance to administer the community's floodplain management ordinance can complete
Sections A, B, C (or E), and G of this Elevation Certificate. Complete the applicable item(s) and sign below. Check the measurement
used in Items G8—G10. In Puerto Rico only, enter meters.
G1. ❑ The information in Section C was taken from other documentation that has been signed and sealed by a licensed surveyor,
engineer, or architect who is authorized by law to certify elevation information. (Indicate the source and date of the elevation
data in the Comments area below.)
G2 ❑ A community official completed Section E for a building located in Zone A (without a FEMA -issued or community -issued BFE)
or Zone AO.
G3. ❑ The following information (Items G4—G10) is provided for community floodplain management purposes.
G4. Permit Number
G5. Date Permit Issued
G6. Date Certificate of
Compliance/Occupancy Issued
G7. This permit has been issued for: ❑
G8. Elevation of as -built lowest floor (including
of the building:
G9. BFE or (in Zone AO) depth of flooding at the
G10. Community's design flood elevation:
New Construction ❑ Substantial Improvement
basement)
❑ feet
❑ meters Datum
❑ meters Datum
building site:
• feet
❑ feet
❑ meters Datum
Local Official's Name Title
Community Name Telephone
Signature Date
Comments (including type of equipment and location, per C2(e), if applicable)
❑ Check here if attachments.
FEMA Form 086-0-33 (7/15)
Replaces all previous editions.
Form Page 4 of 6
ELEVATION CERTIFICATE
BUILDING PHOTOGRAPHS
See Instructions for Item A6.
OMB No. 1660-0008
Expiration Date: November 30, 2018
IMPORTANT: In these spaces, copy the corresponding information from Section A.
FOR INSURANCE COMPANY USE
Building Street Address (including Apt., Unit, Suite, and/or Bldg. No.) or P.O. Route and Box No.
1101 STEVENSON AVE.
Policy Number:
City State ZIP Code
CLEARWATER Florida 33755
Company NAIC Number
If using the Elevation Certificate to obtain NFIP flood insurance, affix at least 2 building photographs below according to the
instructions for Item A6. Identify all photographs with date taken; "Front View" and "Rear View"; and, if required, "Right Side View" and
"Left Side View." When applicable, photographs must show the foundation with representative examples of the flood openings or
vents, as indicated in Section A8. If submitting more photographs than will fit on this page, use the Continuation Page.
2018 9 21 ,'
ar,
4,'{t f. .yM#...
M — ii r.
s i.
Photo One
Photo One Caption FRONT VIEW Clear Photo One
2018911
S
a
k 4,.. . ...
• : ,
___I; .„
.... , ,
,... . .
...
.....
v,
..... _ _...._,
,r,:r.„,,...,,
p. . .Y
-�, '_amu=•'f ..� �..
,� w.e. .. -
,
sAs
Photo Two
Photo Two Caption REAR and RIGHT SIDE Clear Photo Two
FEMA Form 086-0-33 (7/15)
Replaces all previous editions.
Form Page 5 of 6
ELEVATION CERTIFICATE
BUILDING PHOTOGRAPHS
Continuation Page
OMB No. 1660-0008
Expiration Date: November 30, 2018
IMPORTANT: In these spaces, copy the corresponding information from Section A.
FOR INSURANCE COMPANY USE
Building Street Address (including Apt., Unit, Suite, and/or Bldg. No.) or P.O. Route and Box No.
1101 STEVENSON AVE.
Policy Number:
City State ZIP Code
CLEARWATER Florida 33755
Company NAIC Number
If submitting more photographs
with: date taken; "Front
photographs must show
than will fit on the preceding page, affix the additional photographs below. Identify
View" and "Rear View"; and, if required, "Right Side View" and "Left Side View."
the foundation with representative examples of the flood openings or vents, as indicated
all photographs
When applicable,
in Section A8.
-.�.
e>.
,
yam) '!i a :.___
may.. 'f, r
{
Photo Three
Photo Three Caption FRONT AND LEFT SIDE Clear Photo Three
Photo Four
Photo Four
Photo Four Caption Clear Photo Four
FEMA Form 086-0-33 (7/15)
Replaces all previous editions.
Form Page 6 of 6