DRC - DRAFT ACTION AGENDA - 06/02/2016
DRAFT ACTION AGENDA
DEVELOPMENT REVIEW COMMITTEE
Thursday, June 02,2016
8:30 - Staff Review
9:00 AM
Case number:
FLD2016-04011 -- 1810 N BELCHER RD
Owner(s):
Bayway Management Inc
611 W Bay St # A
Tampa, FL 33606270
PHONE: No phone, Fax: No fax, Email: No email
Applicant:Robert Pergolizzi
13825 Icot Blvd., Suite 605
33760
PHONE: (727)524-1818, Fax: (727)524-6090, Email:
Pergo@gulfcoastconsultinginc.Com
Representative:Robert Pergolizzi
Gulfcoast Consulting, Inc
13825 Icot Blvd., Suite 605
33760
PHONE: (727)524-1818, Fax: (727)524-6090, Email:
Pergo@gulfcoastconsultinginc.Com
Location:1.1 acres located at the southwest corner of North Belcher Road and Sunnydale
Boulevard.
Atlas Page:262B
Zoning District:Industrial Research and Technology
Request:The Community Development Board (CDB) is reviewing a Comprehensive Infill
Redevelopment Project in the Commercial (C) District for property located at 1810
North Belcher Road. The project is 20 feet in height, includes 21 parking spaces
and requests allowable flexibility from setbacks and landscaping requirements
(Section 2-704.F and 3-1202.G)
Proposed Use:Retail Sales and Services
Neighborhood
Association(s):
Clearwater Neighborhood Coalition
Presenter:Matthew Jackson, Senior Planner
6/2/20161DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Determination of Complete05/03/2016Jackson
Completeness
Solid Waste Review No Comments05/12/2016Pryor
Traffic Eng Review
Comments05/13/2016Elbo
Engineering Review Comments05/16/2016Simpson
Parks and Rec Review
No Comments05/19/2016Reid
Environmental Review Comments05/20/2016Kessler
Harbor Master Review
No Review Required05/24/2016Jackson
Art Review No Reveiw Required05/24/2016Jackson
Planning Review
Comments05/24/2016Jackson
Fire Review No Comments05/25/2016Schultz
Stormwater Review
Comments05/25/2016Bawany
The DRC reviewed this application with the following comments:
Engineering ReviewGeneral Conditions:
If the proposed project necessitates infrastructure modifications to satisfy the
site-specific water capacity and pressure requirements and/or wastewater
capacity requirements, the modifications shall be completed by the applicant
and at their expense. If underground water mains and hydrants are to be
installed, the installation shall be completed and in service prior to
construction in accordance with Fire Department requirements.
Sheet C2 was reviewed for General Engineering criteria. The additional
details provided in the plan set may have been necessary for other
departmental reviews. Further comments will be forthcoming upon submittal
of a Flexible Development and/or Building Permit Application.
DRC review is a prerequisite for Building Permit review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 30 ON DOCUMENT.
6/2/20162DRC_ActionAgenda
Environmental ReviewGeneral Notes:
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Offsite discharge of produced groundwater from dewatering shall comply with
dewatering guidelines from Florida Department of Environmental Protection
(FDEP), F.A.C. 62-621.300(2).
Additional permits from State agencies, such as the Southwest Florida Water
Management District or Florida Department of Environmental Protection, may
be required. Approval does not relieve the applicant from the requirements to
obtain all other required permits and authorizations. **SEE PAGE 0 ON
DOCUMENT.
Environmental ReviewPrior to issuance of building permit:
Provide location of erosion control measures on plans and provide details.
**SEE PAGE 34 ON DOCUMENT.
Planning ReviewAll Planning conditions are required to be met prior to CDB. **SEE PAGE 0
ON DOCUMENT.
Planning ReviewThroughout the responses to criteria it is mentioned that a specialty bike
shop will be the new business for the property. However, it was mentioned to
staff that the bike shop is no longer interested in the property. If this is the
case, revise the application to only include that retail sales and services use
is proposed, not a specific business unless another specific business is
proposed. **SEE PAGE 7 ON DOCUMENT.
Planning ReviewFor the response to general applicability criterion number four, provide
further information on how the retail use will have less intensive traffic
generated than the former bank use. **SEE PAGE 7 ON DOCUMENT.
Planning ReviewFor the response to general criterion number five, list any other retail sales
and services use within the immediate vicinity. **SEE PAGE 7 ON
DOCUMENT.
Planning ReviewWhen organizing the submittal for CDB, place the comprehensive infill
redevelopment project responses right after page seven of the application.
**SEE PAGE 13 ON DOCUMENT.
Planning ReviewWhen possible, do not used scanned copies of files such as the site plan
which does not need to be signed and sealed. Using the original files, not a
scanned copy makes the document much more legible. **SEE PAGE 29
ON DOCUMENT.
Planning ReviewIf only retail sales and service use is proposed with no possibility of a future
bank, please include a brief narrative as to the use of the canopy and old
teller drive thru lanes. If only retail sales and display are proposed, with no
outdoor component to the retail sales and displays, the canopy and excess
vehicular use area should be removed and landscaping provided. **SEE
PAGE 30 ON DOCUMENT.
Planning ReviewAt the south edge of the dumpster area there is a curb. Have only black
barrel trash been used? Logistically, Im not sure how a dumpster can be
utilized knowing a curb will need to be negotiated when moving the dumpster
out for pick up. Or has Solid Waste historically access the site from the
property to the south with no need to move the dumpster? **SEE PAGE 30
ON DOCUMENT.
6/2/20163DRC_ActionAgenda
Planning ReviewThe chainlink enclosure around the existing dumpster must be removed and
replaced with other means of screening the dumpster such as PVC or wood.
If chainlink is to be used, it must be clad in green or black vinyl and there
must be a continuous hedge along the north, east and west sides of the
fence (as shown) or a non-deciduous vine must be maintained along the
north, east and west sides of the fence. **SEE PAGE 30 ON DOCUMENT.
Planning ReviewPlease address if the existing directional signs are to be removed or
incorporated into a future sign plan. **SEE PAGE 30 ON DOCUMENT.
Planning ReviewIn an effort to better diversify accent trees throughout the City, please
consider replacing the crape myrtle with suitable specie such as Walter
Viburnum, eagelston holly, silver buttonwood, eastern redbud, Nellie R.
Stevens Holly or southern wax myrtle. **SEE PAGE 31 ON DOCUMENT.
Planning ReviewOn the landscape plan, please provide specific detail for each interior
landscape island annotating how the island meets Code requirements such
as 50 percent shrubs and whether or not the island has a tree and what type
of tree. **SEE PAGE 31 ON DOCUMENT.
Planning ReviewPursuant to CDC Section 3-1204.D, add wheel stops to all parking spaces
adjacent to landscaping. **SEE PAGE 31 ON DOCUMENT.
Planning ReviewPursuant to CDC Section 3-1202.C, add a note to the landscape plan that an
automatic permanent irrigation system exists or will be installed providing
complete water coverage for all required and other landscape materials.
**SEE PAGE 31 ON DOCUMENT.
Planning ReviewOn Sheet LA2, notes 62 though 65 need to be on separate lines and not
overlap. **SEE PAGE 32 ON DOCUMENT.
Planning ReviewOn page one of the flexible development application for the description of
request, include if office use is also proposed and if so, specify if a specific
type is contemplated such as bank. **SEE PAGE 2 ON DOCUMENT.
Stormwater ReviewGeneral Comments:
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the City's Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp **SEE PAGE 27 ON DOCUMENT.
Stormwater ReviewPrior to Building Permit:
Please provide reasonable assurance that pond still maintained and
functions as originally permitted **SEE PAGE 27 ON DOCUMENT.
Stormwater ReviewStormwater Review
General Comments:
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the Citys Storm Drainage Design Criteria as found at the
City website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp
6/2/20164DRC_ActionAgenda
Stormwater ReviewStormwater Review
Prior to Building Permit:
Please provide reasonable that pond still maintained and functions as
originally permitted
Traffic Engineering Prior to CDB:
Review
As per 2012 Florida Accessibility Code For Building Construction, Section
206, provide an accessible route from public sidewalk to the building's
accessible entrance meeting ADA standards. **SEE PAGE 34 ON
DOCUMENT.
Traffic Engineering General Note(s):
Review
Applicant shall comply with the current Multimodal Impact Fee Ordinance
and fee schedule which shall be paid prior to a Certificate of Occupancy
(C.O.). The MIF amount for the new bicycle shop is $1448.66.
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 3 ON DOCUMENT.
6/2/20165DRC_ActionAgenda
9:20 AM
Case number:FLD2016-03008 -- 440 GULFVIEW BLVD COMMON
Owner(s):Four Forty West Assn Inc
4151 Woodlands Pkw
Palm Harbor, FL 34685
PHONE: No phone, Fax: No fax, Email: No email
Applicant:Steven Stavrevski
2840 West Bay Drive #287
Belleair Bluffs
PHONE: No phone, Fax: No fax, Email: Info@belleairconstruction.Com
Representative:Steven Stavrevski
Belleair Construction
2840 West Bay Drive #287
Belleair Bluffs
PHONE: No phone, Fax: No fax, Email: Info@belleairconstruction.Com
Location:3.73 acres located at the northwest corner of the South Gulfview Boulevard and
Hamden Drive.
Atlas Page:276A
Zoning District:Tourist
Request:The Community Development Board (CDB) is reviewing a proposed outdoor grill
area for an existing attached dwelling development in the Tourist (T) District for the
property located at 440 South Gulfview Boulevard. The project requests allowable
flexibility from setback requirements (Community Development Code Sections 2-
803.D).
Proposed Use:
Overnight Accomodations
Neighborhood
Association(s):
Clearwater Neighborhood Coalition
Presenter:Matthew Jackson, Senior Planner
6/2/20166DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Determination of Complete05/10/2016Jackson
Completeness
Solid Waste Review No Comments05/12/2016Pryor
Traffic Eng Review
No Comments05/13/2016Elbo
Engineering Review Comments05/16/2016Simpson
Parks and Rec Review
No Comments05/19/2016Reid
Environmental Review Comments05/20/2016Kessler
Fire Review
No Comments05/24/2016Schultz
Stormwater Review Comments05/25/2016Bawany
The DRC reviewed this application with the following comments:
Engineering ReviewGeneral Conditions:
If the proposed project necessitates infrastructure modifications to satisfy the
site-specific water capacity and pressure requirements and/or wastewater
capacity requirements, the modifications shall be completed by the applicant
and at their expense. If underground water mains and hydrants are to be
installed, the installation shall be completed and in service prior to
construction in accordance with Fire Department requirements.
Sheet A-2.0 was reviewed for General Engineering criteria. The additional
details provided in the plan set may have been necessary for other
departmental reviews. Further comments will be forthcoming upon submittal
of a Flexible Development and/or Building Permit Application.
DRC review is a prerequisite for Building Permit review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 8 ON DOCUMENT.
Engineering ReviewPrior to Community Development Board:
Please show the ingress and egress easement (OR5776-PG118) on the site
plan. No permanent structures shall be located in an easement (Section 3-
1909, Community Development Code). **SEE PAGE 8 ON DOCUMENT.
Engineering ReviewPrior to Building Permit:
As per City of Clearwater Reclaimed Water System Ordinances, 32.351, and
32.376, use of potable water for irrigation is prohibited; the irrigation system
shall be hooked up to the reclaimed water system that is available to this site.
**SEE PAGE 8 ON DOCUMENT.
6/2/20167DRC_ActionAgenda
Environmental ReviewGeneral Notes:
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Offsite discharge of produced groundwater from dewatering shall comply with
dewatering guidelines from Florida Department of Environmental Protection
(FDEP), F.A.C. 62-621.300(2).
Additional permits from State agencies, such as the Southwest Florida Water
Management District or Florida Department of Environmental Protection, may
be required. Approval does not relieve the applicant from the requirements to
obtain all other required permits and authorizations. **SEE PAGE 0 ON
DOCUMENT.
Environmental ReviewPrior to issuance of building permit:
No light shall be visible or extend in areas identified as Sea Turtle Nesting
Areas during the nesting season (May 1 to October 31). Those areas where
security and public safety require lighting, alternative light management
approaches shall be applied. Provide evidence of sea turtle-friendly lighting
in accordance with City code and state laws. Additional information is found
on Florida Fish and Wildlife Conservation Commission website including
specific lighting guidelines
(http://myfwc.com/media/418417/SeaTurtle_LightingGuidelines.pdf). **SEE
PAGE7 ON DOCUMENT.
Planning ReviewAll Planning conditions are required to be met prior to CDB. **SEE PAGE 0
ON DOCUMENT.
Planning ReviewFor the affidavit to authorize agent, under number one please list the
property owner. The Pinellas County Property Appraiser lists Four Forty
West Assn, Inc. C/O Progressive Management, Inc. **SEE PAGE 2 ON
DOCUMENT.
Planning ReviewFor the affidavit to authorize agent, complete number two with the property
address. **SEE PAGE 2 ON DOCUMENT.
Planning ReviewFor the affidavit to authorize agent, the form states that Sam Vazquez is the
agent and Sam signed on behalf of the owner. Sam either needs to be
appointed as the agent or authorization needs to be provided stating Sam
can sign on behalf of the property owner. Sam cant fill both roles. **SEE
PAGE 2 ON DOCUMENT.
Planning ReviewFor the affidavit to authorize agent, Maureen Reardon is listed as the
registered name under sunbiz.org. As such, only she can sign the affidavit
unless she provides a signed and notarized authorization for another person.
**SEE PAGE 2 ON DOCUMENT.
Planning ReviewThe case contact listed in the uploaded file should match the agent listed in
the affidavit to authorize agent. **SEE PAGE 2 ON DOCUMENT.
Planning ReviewFor the response to general applicability criterion number one, no specific
details were provided. What is the address of the adjacent hotel? Does the
adjacent hotel have a patio area located seaward of the coastal construction
control line? If so, approximately how much patio area exists in square feet?
**SEE PAGE 3 ON DOCUMENT.
6/2/20168DRC_ActionAgenda
Planning ReviewFor the response to general applicability criterion number two, a more
appropriate response would be The proposed addition to the condominium
is an outdoor patio similar in size and extent as other outdoor areas in the
area and it is not expected to hinder or discourage the appropriate
development and use of adjacent land and buildings or significantly impair
the value thereof. **SEE PAGE 3 ON DOCUMENT.
Planning ReviewFor the response to general applicability criterion number three, a more
appropriate response would be The proposed patio area is not expected to
have any effect on the health or safety or persons residing or working in the
neighborhood of the proposed use.**SEE PAGE 3 ON DOCUMENT.
Planning ReviewFor the response to comprehensive infill redevelopment project criterion
number one, please provide a response as to why there is no other space in
the common area for the outdoor grill that does not need a setback reduction
to the coastal construction control line. **SEE PAGE 4 ON DOCUMENT.
Planning ReviewFor the response to comprehensive infill redevelopment project criterion
number two, please provide specific examples of how the proposal is
consistent with the Comprehensive plan as well as Community development
Code. **SEE PAGE 4 ON DOCUMENT.
Planning ReviewFor the response to comprehensive infill redevelopment project criterion
number three, do not simply restate the criterion and give a bit more
explanation. Staff understands that the proposal is minor so a limited
response is acceptable such as It is expected that due to the minor addition
of outdoor patio area consistent with other patios in the area will have no
impact on the development and improvement of surrounding properties.
**SEE PAGE 4 ON DOCUMENT.
Planning ReviewFor the response to comprehensive infill redevelopment project criterion
number four, do not simply restate the criterion and give a bit more
explanation. Staff understands that the proposal is minor so a limited
response is acceptable such as It is expected that due to the minor addition
of outdoor patio area consistent with other patios in the area, the proposal
will not cause any determent to adjoining properties. **SEE PAGE 4 ON
DOCUMENT.
Planning ReviewFor the response to comprehensive infill redevelopment project criterion
number 6.a, b, c and e, do not simply restate the criterion and give a bit more
explanation. **SEE PAGE 4 ON DOCUMENT.
Planning ReviewWhenever possible, do not use scanned copies of documents, use the
original and save as a PDF for legibility. **SEE PAGE 5 ON DOCUMENT.
Planning ReviewThe north arrows on sheets C-1 and A-2.0 are not oriented correctly. **SEE
PAGE 7 ON DOCUMENT.
Planning ReviewOn Sheet A-2.0, provide the closest dimension from the proposed work to the
coastal construction control line. **SEE PAGE 8 ON DOCUMENT.
Planning ReviewSheet A-2.0 shows a handicapped path from the proposed outdoor kitchen
area but the renderings provided show steps. Clarify which is correct and
update the appropriate document. **SEE PAGE 8 ON DOCUMENT.
Planning ReviewPlanning Review
All Planning conditions are required to be met prior to CDB.
Planning ReviewPlanning Review
For the affidavit to authorize agent, under number one please list the
property owner. The Pinellas County Property Appraiser lists Four Forty
West Assn, Inc. C/O Progressive Management, Inc.
6/2/20169DRC_ActionAgenda
Planning ReviewPlanning Review
For the affidavit to authorize agent, complete number two with the property
address.
Planning ReviewPlanning Review
For the affidavit to authorize agent, the form states that Sam Vazquez is the
agent and Sam signed on behalf of the owner. Sam either needs to be
appointed as the agent or authorization needs to be provided stating Sam
can sign on behalf of the property owner. Sam cant fill both roles.
Planning ReviewPlanning Review
For the affidavit to authorize agent, Maureen Reardon is listed as the
registered name under sunbiz.org. As such, only she can sign the affidavit
unless she provides a signed and notarized authorization for another person.
Planning ReviewPlanning Review
The case contact listed in the uploaded file should match the agent listed in
the affidavit to authorize agent.
Planning ReviewPlanning Review
For the response to comprehensive infill redevelopment project criterion
number two, please provide specific examples of how the proposal is
consistent with the Comprehensive plan as well as Community development
Code.
Planning ReviewPlanning Review
For the response to comprehensive infill redevelopment project criterion
number three, do not simply restate the criterion and give a bit more
explanation. Staff understands that the proposal is minor so a limited
response is acceptable such as It is expected that due to the minor addition
of outdoor patio area consistent with other patios in the area will have no
impact on the development and improvement of surrounding properties.
Planning ReviewPlanning Review
On Sheet A-2.0, provide the closest dimension from the proposed work to the
coastal construction control line.
Planning ReviewPlanning Review
Sheet A-2.0 shows a handicapped path from the proposed outdoor kitchen
area but the renderings provided show steps. Clarify which is correct and
update the appropriate document.
Planning ReviewPlanning Review
For the response to general applicability criterion number one, no specific
details were provided. What is the address of the adjacent hotel? Does the
adjacent hotel have a patio area located seaward of the coastal construction
control line? If so, approximately how much patio area exists in square feet?
Planning ReviewPlanning Review
For the response to general applicability criterion number two, a more
appropriate response would be The proposed addition to the condominium
is an outdoor patio similar in size and extent as other outdoor areas in the
area and it is not expected to hinder or discourage the appropriate
development and use of adjacent land and buildings or significantly impair
the value thereof.
Planning ReviewPlanning Review
For the response to general applicability criterion number three, a more
appropriate response would be The proposed patio area is not expected to
have any effect on the health or safety or persons residing or working in the
neighborhood of the proposed use.
6/2/201610DRC_ActionAgenda
Planning ReviewPlanning Review
For the response to comprehensive infill redevelopment project criterion
number one, please provide a response as to why there is no other space in
the common area for the outdoor grill that does not need a setback reduction
to the coastal construction control line.
Planning ReviewPlanning Review
For the response to comprehensive infill redevelopment project criterion
number four, do not simply restate the criterion and give a bit more
explanation. Staff understands that the proposal is minor so a limited
response is acceptable such as It is expected that due to the minor addition
of outdoor patio area consistent with other patios in the area, the proposal
will not cause any determent to adjoining properties.
Planning ReviewPlanning Review
For the response to comprehensive infill redevelopment project criterion
number6.a, b, c and e, do not simply restate the criterion and give a bit more
explanation.
Planning ReviewPlanning Review
Whenever possible, do not use scanned copies of documents, use the
original and save as a PDF for legibility.
Planning ReviewPlanning Review
The north arrows on sheets C-1 and A-2.0 are not oriented correctly.
Stormwater ReviewGeneral Comments
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 9 ON DOCUMENT.
Stormwater ReviewPrior to Community Development Board:
The City's Storm Drainage Design Criteria defines redevelopment as the
alteration of buildings, parking, or other landform features of a property,
which necessitates the Community Development Code review process.
Please provide rough drainage calculations which meet the Storm Drainage
Design Criteria as found at the City website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp **SEE PAGE 9 ON DOCUMENT.
Stormwater ReviewStormwater Review
General Comments
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
FLD2016-030082327672016-05-2516:02:08.147 STRM - Condition
NBAWANY9 Prior to Community Development Board:
The City's Storm Drainage Design Criteria defines redevelopment as the
alteration of buildings, parking, or other landform features of a property,
which necessitates the Community Development Code review process.
Please provide rough drainage calculations which meet the Storm Drainage
Design Criteria as found at the City website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp
6/2/201611DRC_ActionAgenda
9:35 AM
Case number:FLS2016-05024 -- 2849 GULF TO BAY BLVD
Owner(s):A B/P S R E G Bayview Owner Llc
5605 Glenridge Dr Ste 775
Atlanta, GA 30342137
PHONE: No phone, Fax: No fax, Email: No email
Applicant:
William Givens
380 Park Place Blvd
Clearwater, FL 33759
PHONE: (727)531-3505, Fax: (727)431-1777, Email: Ryan.Givens@cardno.Com
Representative:Ryan Givens
Cardno
380 Park Place Blvd
Clearwater, FL 33759
PHONE: (727)531-3505, Fax: (727)431-1777, Email: Ryan.Givens@cardno.Com
Location:1.15 acres located at the southwest corner of Gulf to Bay Boulevard and Cross
Circle.
Atlas Page:300B
Zoning District:Commercial
Request:The Development Review Committee (DRC) is reviewing a proposed one-story
retail plaza use within the Commercial (C) District for property located at 24849
Gulf to Bay Boulevard. The project includes 49 parking spaces and requests
allowable flexibility of the number of parking spaces for the restaurant portion of the
plaza and required landscaping (Sections 2-703.U, 2-703.V and 3-1202).
Proposed Use:
Retail Sales and Services
Neighborhood
Association(s):
Clearwater Neighborhood Coalition
Presenter:Matthew Jackson, Senior Planner
6/2/201612DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Determination of Complete05/09/2016Jackson
Completeness
Solid Waste Review Comments05/12/2016Pryor
Make sure this is designed and built to specs Index 701, 24'X10' interiorly with ballards and gates
mounted even with wall and not inside.
Engineering Review Comments05/16/2016Simpson
Traffic Eng Review Comments05/18/2016Elbo
Parks and Rec Review No Comments05/19/2016Reid
Environmental Review Comments05/20/2016Kessler
Planning Review Comments05/23/2016Jackson
Stormwater Review Comments05/25/2016Bawany
Land Resource Review Comments05/26/2016Crandall
Fire Review No Comments05/29/2016Schultz
The DRC reviewed this application with the following comments:
Engineering ReviewGeneral Conditions:
If the proposed project necessitates infrastructure modifications to satisfy the
site-specific water capacity and pressure requirements and/or wastewater
capacity requirements, the modifications shall be completed by the applicant
and at their expense. If underground water mains and hydrants are to be
installed, the installation shall be completed and in service prior to
construction in accordance with Fire Department requirements.
Sheet SC3.00 was reviewed for General Engineering criteria. The additional
details provided in the plan set may have been necessary for other
departmental reviews. Further comments will be forthcoming upon submittal
of a Flexible Development and/or Building Permit Application.
DRC review is a prerequisite for Building Permit review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 16 ON DOCUMENT.
Engineering ReviewPrior to Building Permit
Please include City Index 701 or an approved equivalent for the Dumpster
Enclosure detail. **SEE PAGE 16 ON DOCUMENT.
6/2/201613DRC_ActionAgenda
Engineering ReviewPrior to Community Development Board:
The stormwater plan demonstrates the 18" RCP pipe underneath the
dumpster enclosure. It is highly recommended that this pipe or the
dumpsters be relocated. **SEE PAGE 17 ON DOCUMENT.
Environmental ReviewGeneral Notes:
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Offsite discharge of produced groundwater from dewatering shall comply with
dewatering guidelines from Florida Department of Environmental Protection
(FDEP), F.A.C. 62-621.300(2).
Additional permits from State agencies, such as the Southwest Florida Water
Management District or Florida Department of Environmental Protection, may
be required. Approval does not relieve the applicant from the requirements to
obtain all other required permits and authorizations. **SEE PAGE 0 ON
DOCUMENT.
Environmental ReviewPrior to issuance of building permit:
Continue to provide the location of erosion control measures on plans.
**SEE PAGE 15 ON DOCUMENT.
Land Resource ReviewDRC review is a prerequisite for Building Permit Review, prior to issuance of
a building permit any and all performance based erosion and sedimentation
control measures must be approved by Environmental and or Stormwater
Engineering, be installed properly, and inspected. **SEE PAGE 15 ON
DOCUMENT.
Land Resource ReviewPlease note that Royal Palms are not considered specimen palms. Must be
in the phoenix family (excluding those less than 20 feet ct, robelenii)
Revise the front landscape buffer to meet the required number of shade trees
by adding shade trees, specimen palms, additional palms or accent trees.
**SEE PAGE 19 ON DOCUMENT.
Land Resource ReviewGreat selection of tree species. No response to this comment required.
**SEE PAGE 20 ON DOCUMENT.
Planning ReviewOn page two of the memorandum, remove all references to the ITE manual
and only reference parking required by the Commercial District of the
Community Development Code. **SEE PAGE 3 ON DOCUMENT.
Planning ReviewOn page two of the memorandum, the minimum Code required parking is 50,
not 49. 3.175 * 12 plus 2.925 * 4 equals 50 spaces. **SEE PAGE 3 ON
DOCUMENT.
Planning ReviewThe response to restaurant flexibility criteria number two should include that
no direct access to Gulf to Bay is proposed. **SEE PAGE 4 ON
DOCUMENT.
Planning ReviewFor the response to restaurant flexibility criteria number three, as a parapet
wall may extend 42 inches above the allowable height, there is no height
flexibility proposed. Please update the response as such. **SEE PAGE 4
ON DOCUMENT.
6/2/201614DRC_ActionAgenda
Planning ReviewThe response to restaurant flexibility criteria number five states there are no
setbacks proposed below minimum standards. This appears correct on the
site plan but the site plan needs to be updated with setback dimensions
around the entire project. **SEE PAGE 5 ON DOCUMENT.
Planning ReviewProvide a cross access agreement with the property to the west. **SEE
PAGE 5 ON DOCUMENT.
Planning ReviewFor the response to retail plaza flexibility criteria number one, as a parapet
wall may extend 42 inches above the allowable height, there is no height
flexibility proposed. Please update the response as such. **SEE PAGE 5
ON DOCUMENT.
Planning ReviewFor the response to retail plaza flexibility criteria number three, as it is not
necessary, remove all references to the ITE parking generation manual and
only reference parking spaces required by the CDC. Pursuant to CDC
Section 3-1401.C, a parking demand study is only required if the parking
requested is greater than 50 percent of the top end of the range. As less than
a 50 percent deviation is requested, no study is required. **SEE PAGE 6
ON DOCUMENT.
Planning ReviewOn page one of the comprehensive landscape program application, remove
the reference to the off-site sign. Off-site signs are not allowable.
Furthermore, shrubs are not required in front of the freestanding sign and
groundcover can suffice for the required three foot wide landscaping around
the entire base of the sign. Therefore, you can remove the shrub request
from the description of request. **SEE PAGE 7 ON DOCUMENT.
Planning ReviewAll Planning conditions are required before issuance of a development order.
**SEE PAGE 16 ON DOCUMENT.
Planning Review
to be in front of the drive thru restaurant. This will allow the placement of the
sign to be behind the leading edge of the building like the vast majority of
drive thru menu signs on Gulf to Bay. Furthermore, moving the sign will allow
the relocation of the eagleston holly a few feet east to better frame the retail
space. **SEE PAGE 16 ON DOCUMENT.
Planning ReviewOn Sheet SC3.00, as they are not needed, remove all references to the ITE
parking generation. **SEE PAGE 16 ON DOCUMENT.
Planning ReviewOn Sheet L-1, provide the interior island width dimensions. **SEE PAGE
19 ON DOCUMENT.
Planning ReviewOn Sheet L-1, as terminal interior islands are not required, can you combine
landscape islands in order to provide the Code compliant 17 foot width
islands? **SEE PAGE 19 ON DOCUMENT.
Planning ReviewOn Sheet L-1, where parking stalls are adjacent to landscaping, provide
wheel stops along with the shown curbing. **SEE PAGE 19 ON
DOCUMENT.
Planning ReviewOn Sheet L-1, show the required 20 foot sight visibility triangles at the
ingress/ egress onto Cross Circle and relocated any landscaping above 30
inches in height if located within a triangle. **SEE PAGE 19 ON
DOCUMENT.
Planning ReviewOn Sheet L-2, include the symbol next to each landscape material. **SEE
PAGE 20 ON DOCUMENT.
Planning ReviewOn Sheet L-2, add a note that the royal palm trees with have 10 foot clear
trunk. **SEE PAGE 20 ON DOCUMENT.
6/2/201615DRC_ActionAgenda
Planning ReviewThis condition does not need to be addressed but I wanted to provide in
anticipation of reviewing the signs. The signage requested due to signs
being proposed on a non-frontage elevation (south) will need to be requested
through a comprehensive sign program. **SEE PAGE 23 ON DOCUMENT.
Planning ReviewFor the lighting shown on Sheet E-1, pursuant to CDC Section 1302.A, all
light fixtures visible from the boundaries of the site, other than fixtures which
are designed and installed to illuminate a wall and are directed away from
adjacent properties, the fixtures shall be cut-off above 40 degrees horizontal.
As such, on Sheet E-1, discuss how compliance with the Code Section is
met. **SEE PAGE 24 ON DOCUMENT.
Planning ReviewFor the lighting shown on Sheet E-1, pursuant to CDC Section 1302.C.1, for
cut-off fixtures, the height of the lamp in a light fixture shall not exceed 35
feet, or one foot in height for each one foot the light fixture is setback from
the setback, whichever is less. As such, on Sheet E-1, discuss how
compliance with the Code Section is met. **SEE PAGE 24 ON
DOCUMENT.
Planning ReviewOn Sheet L-1, pursuant to CDC Section 3-1202.B.1, for the palm trees to be
counted as shade trees, they must be in clusters of three. **SEE PAGE 19
ON DOCUMENT.
Solid Waste ReviewMake sure this is designed and built to specs Index 701, 24'X10' interiorly
with ballards and gates mounted even with wall and not inside.
Stormwater ReviewGeneral Comments:
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 17 ON DOCUMENT.
Stormwater ReviewPrior to Building Permit:
Please provide original stormwater report which demonstrates that this
projects impervious was properly accounted for in the master drainage
system. Note: the current site must meet the current drainage criteria.
Please refer to the Citys Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp **SEE PAGE 17 ON DOCUMENT.
Stormwater ReviewStormwater Review
General Comments:
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Stormwater ReviewStormwater Review
Prior to Building Permit:
Please provide original stormwater report which demonstrates that this
projects impervious was properly accounted for in the master drainage
system. Note: the current site must meet the current drainage criteria.
Please refer to the Citys Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp
6/2/201616DRC_ActionAgenda
Stormwater ReviewPrior to Building Permit:
Please provide reasonable assurance that the site will be graded so that
stormwater does not drain to the property to the west
(17/29/16/03006/000/0204). **SEE PAGE 17 ON DOCUMENT.
Traffic Engineering Prior to a building permit:
Review
Provide wheel stops in parking stalls that abuts a sidewalk to prevent vehicle
overhanging onto the pedestrian walkway. **SEE PAGE 16 ON
DOCUMENT.
Traffic Engineering Prior to a building permit:
Review
Drive-through facilities for restaurants shall provide sufficient stacking
distance to accommodate eight vehicles as measured from the first point of
transaction. Please show this on the site plan using a scaled 19' long vehicle
(AASHTO standards) with a 1' gap between bumpers. (Community
Development Code, Section 3-1406 B.) **SEE PAGE 16 ON DOCUMENT.
Traffic Engineering General Note(s):
Review
Applicant shall comply with the current Multimodal Impact Fee Ordinance
and fee schedule which shall be paid prior to a Certificate of Occupancy.
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 16 ON DOCUMENT.
Traffic Engineering Prior to a building permit:
Review
There is a potential conflict point for the inbound traffic off of Cross
Boulevard and the south & east bound on site traffic circulation. Please
provide a stop sign and stop bar for both the south & east bound on site
traffic circulation. **SEE PAGE 16 ON DOCUMENT.
Traffic Engineering Prior to a DO:
Review
This proposed project will require a Traffic Impact Study (TIS). Prior to
conducting a TIS please schedule a scoping meeting with the Traffic
Operations Division. **SEE PAGE 16 ON DOCUMENT.
6/2/201617DRC_ActionAgenda
10:35 AM
Case number:FLD2016-03007 -- 1861 N Highland
Owner(s):
PHONE: No phone, Fax: No fax, Email: No email
Applicant:
Stephen Fowler
1421 Court St
Clearwater, FL 33756
PHONE: (727)449-2021, Fax: (727)447-5339, Email: Overdrawn5@aol.Com
Representative:Stephen Fowler
Fowler Associates Architects, Inc.
1421 Court St
Clearwater, FL 33756
PHONE: (727)449-2021, Fax: (727)447-5339, Email: Overdrawn5@aol.Com
Location:8.7 acres located at the southeast corner of North Highland Avenue with Sunset
Point Road.
Atlas Page:261A
Zoning District:Commercial
Request:The Community Development Board (CDB) is reviewing a Comprehensive Infill
Redevelopment Project in the Commercial (C) District for property located at 1861
N. Highland Avenue. The project is 32 feet in height, includes 408 parking spaces
and requests allowable flexibility from setbacks and landscaping requirements
(Section 2-704.F and 3-1202.G)
Proposed Use:
Self-Storage Warehouse
Neighborhood
Association(s):
Clearwater Neighborhood Coalition
Presenter:Melissa Hauck-Baker, Senior Planner
6/2/201618DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Determination of Complete05/03/2016Hauck-Baker
Completeness
Solid Waste Review Comments05/12/2016Pryor
No plans for solid waste on out parcel
Engineering Review Comments05/16/2016Simpson
Traffic Eng Review Comments05/19/2016Elbo
Parks and Rec Review No Comments05/19/2016Reid
Fire Review Comments05/20/2016Schultz
Environmental Review Comments05/20/2016Kessler
Planning Review Comments05/24/2016Hauck-Baker
Stormwater Review Comments05/25/2016Bawany
Route to Meeting Ready for DRC06/01/2016Hauck-Baker
Land Resource Review Comments06/01/2016Anderson
Harbor Master Review No Review Required06/01/2016Hauck-Baker
Art Review No Reveiw Required06/01/2016Hauck-Baker
The DRC reviewed this application with the following comments:
6/2/201619DRC_ActionAgenda
Engineering ReviewGeneral Conditions:
If the proposed project necessitates infrastructure modifications to satisfy the
site-specific water capacity and pressure requirements and/or wastewater
capacity requirements, the modifications shall be completed by the applicant
and at their expense. If underground water mains and hydrants are to be
installed, the installation shall be completed and in service prior to
construction in accordance with Fire Department requirements.
Sheet SD-01 was reviewed for General Engineering criteria. The additional
details provided in the plan set may have been necessary for other
departmental reviews. Further comments will be forthcoming upon submittal
of a Flexible Development and/or Building Permit Application.
DRC review is a prerequisite for Building Permit review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 32 ON DOCUMENT.
Engineering ReviewPrior to CDB:
Please acknowledge the following; the existing dumpster enclosure is
located in an easement. NOTE: any structure approved for location in an
easement may be removed or displaced by city forces if that structure
interferes with the maintenance or use of the Easement Rights. **SEE
PAGE32 ON DOCUMENT.
Engineering ReviewPrior to CDB:
If the new out-parcel is to have separate ownership from the existing 1861 N.
Highland, then it will need to be a separate property. It is encouraged to use
a plat as the mechanism for creating this new property boundary. The new
property boundary will need to be in place before a building permit is
approved for the construction of the new building. **SEE PAGE 32 ON
DOCUMENT.
Environmental ReviewGeneral Notes:
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Offsite discharge of produced groundwater from dewatering shall comply with
dewatering guidelines from Florida Department of Environmental Protection
(FDEP), F.A.C. 62-621.300(2).
Additional permits from State agencies, such as the Southwest Florida Water
Management District or Florida Department of Environmental Protection, may
be required. Approval does not relieve the applicant from the requirements to
obtain all other required permits and authorizations. **SEE PAGE 0 ON
DOCUMENT.
Fire ReviewTamper switches are required to be installed on the fire supply DDCV and
must be connected to the FACP. Please acknowledge. **SEE PAGE 32
ON DOCUMENT.
6/2/201620DRC_ActionAgenda
Fire ReviewNFPA 1 2010 edition section 13.3.2.27.4 requires fire sprinkler system for
building. Shall meet the requirement of NFPA 13 2010 edition section 4.1
Level of Protection. Any and all changes, additions, relocations,
improvements, and/or modifications to the fire sprinkler system at this
property must be done as per NFPA-13 2010 edition by a licensed fire
sprinkler contractor with separate permit and plans. Please acknowledge
prior to CDB. **SEE PAGE 32 ON DOCUMENT.
Fire ReviewAll underground fire lines must be installed by a contractor with a class I, II or
V license with separate plans and permit. Acknowledge PRIOR TO CDB.
**SEE PAGE 32 ON DOCUMENT.
Fire ReviewNew parcel shown on plans. Please provide details or remove from plans.
**SEE PAGE 32 ON DOCUMENT.
Land Resource ReviewGeneral Note:
1.
DRC review is a prerequisite for Building Permit Review, prior to
issuance of a building permit any and all performance based erosion and
sedimentation control measures must be approved by Environmental and or
Stormwater Engineering, be installed properly, and inspected. **SEE
PAGE32 ON DOCUMENT.
Land Resource ReviewPrior to CDB:
Code section 4-202 A 11.aa. requires a tree inventory to be prepared by
a certified arborist reflecting the size, canopy, and condition of such trees.
Once this data is received a thorough review can be conducted. At such time
comments can be generated which may require modifications to the plans.
No review will be performed until the inventory is received. Provide prior to
CDB. This is required for the entire site to ensure there are no Hazardous
trees on the site. **SEE PAGE 33 ON DOCUMENT.
Land Resource ReviewPrior to Issuance of a Building Permit:
1. Shade trees must be installed in the landscape. The interior islands
proposed are smaller than code requires but are still large enough for shade
trees. Bottlebrush and Crape Myrtles are not shade trees. **SEE PAGE 33
ON DOCUMENT.
Land Resource ReviewPrior to issuance of a Building Permit:
A tree removal permit will be required for the removal of any trees needed to
be removed for the demo of existing conditions or the construction of the new
proposed out parcel. **SEE PAGE 33 ON DOCUMENT.
Land Resource ReviewGeneral Note:
Due to the improper maintenance of Crape Myrtles mainly topping and
shaping of them they are currently not an acceptable species for commercial
sites. as per MLD **SEE PAGE 33 ON DOCUMENT.
Land Resource ReviewPrior to CDB:
1. The proposed landscape islands do not meet minimum code and will
require a comprehensive landscape program. **SEE PAGE 33 ON
DOCUMENT.
6/2/201621DRC_ActionAgenda
Land Resource ReviewPrior to CDB:
1. You need to show a tree removal and replacement chart to clearly show
the inches to be removed and the inches proposed. **SEE PAGE 33 ON
DOCUMENT.
Land Resource ReviewPrior to issuance of a building permit:
1. Please clearly mark any existing trees with an "X" to clearly show they are
proposed to be removed. **SEE PAGE 33 ON DOCUMENT.
Land Resource ReviewLand Resource Review
1.
DRC review is a prerequisite for Building Permit Review, prior to
issuance of a building permit any and all performance based erosion and
sedimentation control measures must be approved by Environmental and or
Stormwater Engineering, be installed properly, and inspected.
Land Resource ReviewLand Resource Review
Prior to CDB:
Code section 4-202 A 11.aa. requires a tree inventory to be prepared by
a certified arborist reflecting the size, canopy, and condition of such trees.
Once this data is received a thorough review can be conducted. At such time
comments can be generated which may require modifications to the plans.
No review will be performed until the inventory is received. Provide prior to
CDB. This is required for the entire site to ensure there are no Hazardous
trees on the site.
Land Resource ReviewLand Resource Review
Prior to Issuance of a Building Permit:
1. Shade trees must be installed in the landscape. The interior islands
proposed are smaller than code requires but are still large enough for shade
trees. Bottlebrush and Crape Myrtles are not shade trees.
Land Resource ReviewLand Resource Review
Prior to issuance of a Building Permit:
A tree removal permit will be required for the removal of any trees needed to
be removed for the demo of existing conditions or the construction of the new
proposed out parcel.
Land Resource ReviewLand Resource Review
General Note:
Due to the improper maintenance of Crape Myrtles mainly topping and
shaping of them they are currently not an acceptable species for commercial
sites. as per MLD
Land Resource ReviewLand Resource Review
1. The proposed landscape islands do not meet minimum code and will
require a comprehensive landscape program.
Land Resource ReviewLand Resource Review
1. You need to show a tree removal and replacement chart to clearly show
the inches to be removed and the inches proposed.
Land Resource ReviewLand Resource Review
1. Please clearly mark any existing trees with an "X" to clearly show they are
proposed to be removed.
6/2/201622DRC_ActionAgenda
Planning ReviewGeneral Site Plan and Application Comments
1. Survey does not reflect existing site conditions, please provide an
updated survey.
2. Parking space breakdown has not been provided; please provide details
regarding percentage of restaurant floor area versus total retail plaza.
3. The proposed outparcel in parking lot will create a land locked parcel.
4. A plat for the proposed outparcel was not submitted.
5. Please show how the proposed outparcel will comply with use, parking,
buffers, landscaping and site circulation.
6. The landscaping plan includes crape myrtle plants, please provide a
substitute.
7. Clarify that the light fixtures either existing or relocated will not conflict with
parking spaces.
8. Architectural floor plan and elevations of south and east facing walls have
not been submitted with application. **SEE PAGE 0 ON DOCUMENT.
Planning ReviewPlanning Review:
1. Survey does not reflect existing site conditions, please provide an updated
survey.
2. Parking space breakdown has not been provided; please provide details
regarding percentage of restaurant floor area versus total retail plaza.
3. The proposed outparcel in parking lot will create a land locked parcel.
4. A plat for the proposed outparcel was not submitted.
5. Please show how the proposed outparcel will comply with use, parking,
buffers, landscaping and site circulation.
6. The landscaping plan includes crape myrtle plants, please provide a
substitute.
7. Clarify that the light fixtures either existing or relocated will not conflict with
parking spaces.
8. Architectural floor plan and elevations of south and east facing walls have
not been submitted with application.
9. A Comprehensive Landscaping Program application has not been
submitted and the applicant shall consider submitting one.
Solid Waste ReviewNo plans for solid waste on out parcel.
Stormwater ReviewGeneral Comments:
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 32 ON DOCUMENT.
Stormwater ReviewPrior to Community Development Board:
The City's Storm Drainage Design Criteria defines redevelopment as the
alteration of buildings, parking, or other landform features of a property,
which necessitates the Community Development Code review process.
Please provide rough drainage calculations which meet the Storm Drainage
Design Criteria as found at the City website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp **SEE PAGE 32 ON DOCUMENT.
6/2/201623DRC_ActionAgenda
Traffic Engineering Prior to a building permit:
Review
There is a potential conflict point for the inbound traffic off of south driveway
of Highland Avenue and the south bound on site traffic circulation. Please
provide a stop sign and stop bar for the south bound on site traffic circulation.
**SEE PAGE 32 ON DOCUMENT.
Traffic Engineering Prior to a building permit:
Review
There is a potential conflict point for the inbound traffic off of the middle
driveway of Highland Avenue and the north bound on site traffic circulation.
Please provide a stop sign and stop bar for the north bound on site traffic
circulation. **SEE PAGE 32 ON DOCUMENT.
Traffic Engineering Prior to CDB:
Review
Disperse accessible parking spaces to the nearest accessible entrance of the
Dollar General and Auto Parts store. (2012 Florida Accessibility Code For
Building Construction Section, 208.3.1) **SEE PAGE 32 ON DOCUMENT.
Traffic Engineering General Note(s):
Review
Applicant shall comply with the current Multimodal Impact Fees Ordinance
and fee schedule which shall be paid prior to a Certificate of Occupancy
(C.O.). The MIF amount for the new retail is $19,866.60.
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 32 ON DOCUMENT.
Traffic Engineering Prior to CDB:
Review
Provide an accessible route from a buildings accessible entrance to a public
sidewalk along Highland Avenue. (2012 Florida Accessibility Code for
Building Construction, Section 206.2.1) **SEE PAGE 32 ON DOCUMENT.
Traffic Engineering Prior to a building permit:
Review
Provide a wheel stop in the parking stalls which abut a sidewalk to prevent
parked vehicles from overhanging onto the pedestrian walkway.
**SEE PAGE 32 ON DOCUMENT.
Traffic Engineering Prior to a building permit:
Review
Add city standard accessible parking stall and sign details, use web link
provided for the details (see Index 118 and 119).
http://www.myclearwater.com/gov/depts/pwa/engin/Production/stddet/index.a
sp
All traffic control devices (signs and markings) shall comply with standards
set forth by the current Manual on Uniform Traffic Control Devices
(MUTCD). (Development Code Section: 3-1410) **SEE PAGE 32 ON
DOCUMENT.
6/2/201624DRC_ActionAgenda
11:05 AM
Case number:FLD2016-05012 -- 314 S MISSOURI AVE 2 FL
Owner(s):Disi-jbe Llc
Po Box 10286
Largo, FL 33773028
PHONE: No phone, Fax: No fax, Email: No email
Applicant:Jeannie Shapiro
707 N. Fort Harrison Ave
Clearwater
PHONE: No phone, Fax: No fax, Email: Jshapiro@clearwaterfreeclinic.Org
Representative:Brian Barker
Deuel & Associates
565 S. Hercules Ave
Clearwater, FL 33764
PHONE: (727)822-4151, Fax: (727)821-7255, Email:
Brian@deuelengineering.Com
Location:1.158 acres located at the northwest corner of South Missouri Avenue with Gould
Street.
Atlas Page:287A
Zoning District:Downtown
Request:The Community Development Board (CDB) is reviewing a Comprehensive Infill
Redevelopment Project in the Downtown (D) District for property located at 314
South Missouri Avenue. The project is 39.33 feet in height, includes 83 parking
spaces and requests allowable flexibility from setbacks, parking and landscaping
requirements (Section 2-903.D and 3-1202.G)
Proposed Use:Medical Clinic
Neighborhood
Association(s):
Clearwater Neighborhood Coalition
Presenter:
Melissa Hauck-Baker, Senior Planner
6/2/201625DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Determination of Complete05/05/2016Hauck-Baker
Completeness
Solid Waste Review Comments05/12/2016Pryor
No dimensions or enclosure plans. Please give me drawing and dimensions of enclosure.
Engineering Review Comments05/16/2016Simpson
Parks and Rec Review No Comments05/19/2016Reid
Environmental Review Comments05/20/2016Kessler
Traffic Eng Review Comments05/20/2016Elbo
Fire Review Comments05/25/2016Schultz
Stormwater Review Comments05/25/2016Bawany
Planning Review Comments05/25/2016Hauck-Baker
Land Resource Review Comments05/26/2016Crandall
Harbor Master Review No Review Required06/01/2016Hauck-Baker
Art Review No Reveiw Required06/01/2016Hauck-Baker
Route to Meeting Ready for DRC06/01/2016Hauck-Baker
The DRC reviewed this application with the following comments:
Engineering ReviewPrior to Certificate of Occupancy
Please provide a 10-ft utility easement over the Waterline that passes
through the property (Section 3-1909, Community Development Code).
Contact Jim Benwell (727.562.4754) for easement requests **SEE PAGE
14 ON DOCUMENT.
Engineering ReviewPrior to Building Permit
As per Community Development Code Section 3-1907B, Sidewalks/Bicycle
paths and City Construction Standard Index No. 109 for Sidewalks, Applicant
shall bring all sub-standard sidewalks and sidewalk ramps adjacent to or a
part of the project up to standard, including A.D.A. standards (raised
detectable tactile surfaces or truncated domes per most recent FDOT Indices
#304 and 310). **SEE PAGE 14 ON DOCUMENT.
6/2/201626DRC_ActionAgenda
Engineering ReviewGeneral Conditions:
If the proposed project necessitates infrastructure modifications to satisfy the
site-specific water capacity and pressure requirements and/or wastewater
capacity requirements, the modifications shall be completed by the applicant
and at their expense. If underground water mains and hydrants are to be
installed, the installation shall be completed and in service prior to
construction in accordance with Fire Department requirements.
Sheet3 was reviewed for General Engineering criteria. The additional
details provided in the plan set may have been necessary for other
departmental reviews. Further comments will be forthcoming upon submittal
of a Flexible Development and/or Building Permit Application.
DRC review is a prerequisite for Building Permit review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 14 ON DOCUMENT.
Engineering ReviewEngineering Review
General Comments
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the Citys Storm Drainage Design Criteria as found at the
City website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp
Engineering ReviewPrior to Community Development Board: It appears that the dumpster is
currently partially located on the neighboring property. Please move
dumpster to be entirely on 314 S. Missouri or provide evidence of a recorded
easement to maintain current configuration. **SEE PAGE 14 ON
DOCUMENT.
Environmental ReviewGeneral Notes:
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Offsite discharge of produced groundwater from dewatering shall comply with
dewatering guidelines from Florida Department of Environmental Protection
(FDEP), F.A.C. 62-621.300(2).
Additional permits from State agencies, such as the Southwest Florida Water
Management District or Florida Department of Environmental Protection, may
be required. Approval does not relieve the applicant from the requirements to
obtain all other required permits and authorizations. **SEE PAGE 0 ON
DOCUMENT.
Environmental ReviewPrior to issuance of building permit:
An Asbestos Survey is usually required prior to conducting any demolition or
renovations. Contact Pinellas County Air Quality (727/464-4422) for more
information. **SEE PAGE 14 ON DOCUMENT.
6/2/201627DRC_ActionAgenda
Fire ReviewTo allow for fire department operations, a fire hydrant shall be located on the
same side of the street and within 300 feet of the building entrance. Please
provide details. **SEE PAGE 13 ON DOCUMENT.
Fire ReviewFire Review
To allow for fire department operations, a fire hydrant shall be located on the
same side of the street and within 300 feet of the building entrance. Please
provide details.
Land Resource ReviewAt time of building permit a tree removal permit will be required to remove the
palms in front. **SEE PAGE 13 ON DOCUMENT.
Land Resource ReviewClarify that 10 percent of the total parking area is provided as greenspace
with landscaping. **SEE PAGE 14 ON DOCUMENT.
Land Resource ReviewThe landscape island in the back (west) has no curbing as required by code.
Provide curbing around landscape island. **SEE PAGE 14 ON
DOCUMENT.
Land Resource ReviewThere is room in the front (east) side of the building for asphalt to be
removed and a larger landscape area. Remove the asphalt to better comply
with the landscaping requirements. **SEE PAGE 14 ON DOCUMENT.
Land Resource ReviewRemove the half dead chinaberry tree on the west property line. **SEE
PAGE 14 ON DOCUMENT.
Land Resource ReviewIf the southern parking lot were to be re-arranged it appears that many more
parking spaces could fit. With more parking spaces more interior green
space islands would be able to be added to bring the landscaping into
greater compliance without reducing the parking. **SEE PAGE 14 ON
DOCUMENT.
Land Resource ReviewGrass is not accepted for landscaping. Provide landscaping in all the grass
areas in the parking islands and buffers. **SEE PAGE 14 ON DOCUMENT.
Land Resource ReviewLand Resource Review
At time of building permit a tree removal permit will be required to remove the
palms in front.
Land Resource ReviewLand Resource Review
The landscape island in the back (west) has no curbing as required by code.
Provide curbing around landscape island.
Land Resource ReviewLand Resource Review
There is room in the front (east) side of the building for asphalt to be
removed and a larger landscape area. Remove the asphalt to better comply
with the landscaping requirements.
Planning ReviewGeneral Site Plan and Application Comments
1. The existing trash enclosure encroaches onto the adjacent property to
the north. Please relocate the trash enclosure completely within the subject
property.
2. The subject property is located within the Town Lake Business Park area
of the Downtown Redevelopment Plan; please address the character district
criteria and the design guidelines. **SEE PAGE 0 ON DOCUMENT.
6/2/201628DRC_ActionAgenda
Planning ReviewPlanning Review
General Site Plan and Application Comments
1. The existing trash enclosure encroaches onto the adjacent property to
the north. Please relocate the trash enclosure completely within the subject
property.
2. The subject property is located within the Town Lake Business Park area
of the Downtown Redevelopment Plan; please address the character district
criteria and the design guidelines.
Solid Waste ReviewNo dimensions or enclosure plans. Please give me drawing and dimensions
of enclosure.
Stormwater ReviewGeneral Comments
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the City's Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp **SEE PAGE 13 ON DOCUMENT.
Traffic Engineering Prior to CDB:
Review
Remove the ramp on all accessible aisles adjacent to the accessible parking
stalls.
Provide wheel stops in the parking stalls which abut a sidewalk to prevent
parked vehicles from overhanging onto the pedestrian walkway.
All parking spaces and drive aisles shall be to current city standards e.g. 9' x
18' parking stall and 24' wide drive aisle (See City Index 120). **SEE
PAGE14 ON DOCUMENT.
6/2/201629DRC_ActionAgenda
11:50 AM
Case number:FLS2016-05023 -- 26508 US HIGHWAY 19 N A
Owner(s):W P G Countryside Llc
2502 N Rocky Point Dr Ste 865
Tampa, FL 33607144
PHONE: No phone, Fax: No fax, Email: No email
Applicant:John Hettick
2502 N. Rocky Point Drive, Suite 865
Tampa
PHONE: No phone, Fax: No fax, Email: Jhettick@wagspg.Com
Representative:Katherine Cole
Hill Ward Henderson
21 Evonaire Circle
Belleair, FL 33756
PHONE: (727)581-1893, Fax: No fax, Email: Katie.Cole@hwhlaw.Com
Location:The subject property is 26508 US Highway 19 North, consists of 3.36 acres (146,
538 SF) and is located at the southwestern intersection of Countryside Boulevard
with US Highway 19 North.
Atlas Page:221B
Zoning District:Tourist
Request:The Development Review Committee (DRC) is reviewing a proposed one story
retail plaza with automobile service station use within the Commercial (C) District
for property located at 26508 US Highway 19 North. The project is 30.08 feet in
height, features 121 parking spaces and requests allowable flexibility of height,
loading space and landscaping (Section 2-703.D, 2-703.V, 3-1202 and 3-1406).
Proposed Use:Retail Sales and Services
Neighborhood
Association(s):
Clearwater Neighborhood Coalition
Presenter:
Melissa Hauck-Baker, Senior Planner
6/2/201630DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Determination of Complete05/05/2016Hauck-Baker
Completeness
Solid Waste Review Comments05/12/2016Pryor
Make sure the single enclosure is 12' X 10' and double is 24' X 10'
Engineering Review Comments05/16/2016Simpson
Traffic Eng Review Comments05/17/2016Elbo
Parks and Rec Review No Comments05/17/2016Reid
Environmental Review Comments05/20/2016Kessler
Planning Review Comments05/24/2016Hauck-Baker
Stormwater Review Comments05/25/2016Bawany
Land Resource Review Comments05/26/2016Crandall
Fire Review No Comments05/29/2016Schultz
Harbor Master Review No Review Required06/01/2016Hauck-Baker
Route to Meeting Ready for DRC06/01/2016Hauck-Baker
Art Review No Review Required06/01/2016Hauck-Baker
The DRC reviewed this application with the following comments:
Engineering ReviewPrior to Building Permit:
Please provide the following notes to the demolition plan:
- All utilities shall be cut and capped prior to demolition. The Wastewater
Supervisor shall be notified.
- All existing utilities shall be protected during demolition.
- Demolition shall not cause any service interruptions for other utility
customers.
- Water meters, double-detector checks and backflow preventers are owned
by the City of Clearwater. The City shall remove and retain these items.
**SEE PAGE 5 ON DOCUMENT.
6/2/201631DRC_ActionAgenda
Engineering ReviewGeneral Conditions:
If the proposed project necessitates infrastructure modifications to satisfy the
site-specific water capacity and pressure requirements and/or wastewater
capacity requirements, the modifications shall be completed by the applicant
and at their expense. If underground water mains and hydrants are to be
installed, the installation shall be completed and in service prior to
construction in accordance with Fire Department requirements.
Sheet F-1 was reviewed for General Engineering criteria. The additional
details provided in the plan set may have been necessary for other
departmental reviews. Further comments will be forthcoming upon submittal
of a Flexible Development and/or Building Permit Application.
DRC review is a prerequisite for Building Permit review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 5 ON DOCUMENT.
Engineering ReviewPrior to Building Permit:
Any work in Countryside Blvd. right of way will require a city right of way use
permit which is permitted through the Engineering Department. Right of way
permits can be found online at
<http://myclearwater.com/gov/depts/pwa/engin/FormsApplications.asp>.
**SEE PAGE 5 ON DOCUMENT.
Engineering ReviewPrior to Building Permit:
As per Community Development Code Section 3-1907B, Sidewalks/Bicycle
paths and City Construction Standard Index No. 109 for Sidewalks, Applicant
shall bring all sub-standard sidewalks and sidewalk ramps adjacent to or a
part of the project up to standard, including A.D.A. standards (raised
detectable tactile surfaces or truncated domes per most recent FDOT
Indexes#304 and 310). **SEE PAGE 5 ON DOCUMENT.
Engineering ReviewPrior to Certificate of Occupancy
Please provide a 10-ft utility easement over the Waterline that passes
through the property (Section 3-1909, Community Development Code).
Contact Jim Benwell (727.562.4754) for easement requests. **SEE PAGE
5 ON DOCUMENT.
Engineering ReviewPrior to Certificate of Occupancy
Please provide a copy of Florida Department of Transportation Right of Way
permit for work on US Highway 19 Right of Way. **SEE PAGE 5 ON
DOCUMENT.
Engineering ReviewPrior to Development Order:
Please acknowledge the following; if multiple buildings will have separate
ownership on the same property, new property boundaries will need to be
created. It is encouraged to use a plat as the mechanism for creating this
before a building permit is approved for the construction of a second building
on a single property. **SEE PAGE 5 ON DOCUMENT.
6/2/201632DRC_ActionAgenda
Environmental ReviewGeneral Notes:
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Offsite discharge of produced groundwater from dewatering shall comply with
dewatering guidelines from Florida Department of Environmental Protection
(FDEP), F.A.C. 62-621.300(2).
Additional permits from State agencies, such as the Southwest Florida Water
Management District or Florida Department of Environmental Protection, may
be required. Approval does not relieve the applicant from the requirements to
obtain all other required permits and authorizations. **SEE PAGE 0 ON
DOCUMENT.
Environmental ReviewPrior to issuance of building permit:
Provide the location erosion control measures on plan sheet and provide
detail notes. **SEE PAGE 5 ON DOCUMENT.
Land Resource ReviewProvide a Tree Preservation Plan prepared by an ISA Certified Arborist. This
plan must show how the proposed building, parking, stormwater, irrigation
and utilities impact the critical root zones (drip lines) of trees to be preserved
and how you propose to address these impacts i.e.; crown elevating, root
pruning and/or root aeration systems. Other data required on this plan must
show the trees canopy line, actual tree barricade limits (2/3 of the drip line
and/or in the root prune lines if required), and the tree barricade detail. And
any other pertinent information relating to tree preservation. Provide prior to
building permit and it must address the off site trees near the proposed pond.
Provide prior to **SEE PAGE 5 ON DOCUMENT.
Land Resource ReviewDRC review is a prerequisite for Building Permit Review, prior to issuance of
a building permit any and all performance based erosion and sedimentation
control measures must be approved by Environmental and or Stormwater
Engineering, be installed properly, and inspected. **SEE PAGE 5 ON
DOCUMENT.
Land Resource ReviewProvide a tree survey and inventory. **SEE PAGE 6 ON DOCUMENT.
Land Resource ReviewGreat selection of tree species. No response is needed for this comment.
**SEE PAGE 6 ON DOCUMENT.
Land Resource ReviewLand Resource Review
Provide a Tree Preservation Plan prepared by an ISA Certified Arborist. This
plan must show how the proposed building, parking, stormwater, irrigation
and utilities impact the critical root zones (drip lines) of trees to be preserved
and how you propose to address these impacts i.e.; crown elevating, root
pruning and/or root aeration systems. Other data required on this plan must
show the trees canopy line, actual tree barricade limits (2/3 of the drip line
and/or in the root prune lines if required), and the tree barricade detail. And
any other pertinent information relating to tree preservation. Provide prior to
building permit and it must address the off site trees near the proposed pond.
Provide prior to
FLS2016-050232315672016-05-2515:32:27.823 LR - Condition
ECRANDALL5 DRC review is a prerequisite for Building Permit Review,
prior to issuance of a building permit any and all performance based erosion
and sedimentation control measures must be approved by Environmental
and or Stormwater Engineering, be installed properly, and inspected.
6/2/201633DRC_ActionAgenda
Planning ReviewGeneral Site Plan and Application Comments
1. The proposed number of parking spaces exceeds the requirement by
16 spaces.
2. The proposed parking space size within the Wawa portion of the site
exceeds the required dimension, please revise to 9 ft. by 18 ft.
3. The building of height of the Wawa building exceeds the permitted
maximum height of 25 feet.
4. The interior landscaping percentage proposed is 6.97% and shall be
increased to a minimum of 10%.
5. The loading area for the retail tenant space is located adjacent to the
stormwater pond within the southwest portion of the lot. The location does
not appear to be efficient or useful for the tenant spaces, please provide
clarification regarding the function of the loading space with respect to the
tenants.
6. Please clarify that the light fixtures proposed onsite will not conflict with
required setbacks and sight distance triangles. Additionally, ensure that light
will not spill out onto adjacent parcels. **SEE PAGE 0 ON DOCUMENT.
Solid Waste ReviewMake sure the single enclosure is 12' X 10' and double is 24' X 10'
Stormwater ReviewStormwater Review
Prior to Building Permit:
Please design the stormwater pond with a minimum of 6 in of freeboard from
the top of control structure to top of bank, and demonstrate on stormwater
pond detail.
Stormwater ReviewStormwater Review
Prior to Building Permit:
Please design the stormwater pond with a minimum 6 in of clearance from
the bottom of the pond to the seasonal high water table, and provide a detail
to show the pond cross section.
Stormwater ReviewStormwater Review
Prior to Building Permit:
Please provide reasonable assurance that exiting storm pipes used for outfall
are in adequate condition and properly sized.
Stormwater ReviewStormwater Review
General Comments
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the Citys Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp
Stormwater ReviewStormwater Review
Prior to Building Permit:
Please provide a control structure detail.
Stormwater ReviewStormwater Review
Prior to Building Permit:
Please resubmit drainage calculations which show that out-parcel impervious
amount has not been exceeded with new submittal.
6/2/201634DRC_ActionAgenda
Stormwater ReviewStormwater Review
Prior to Development Order:
Retaining walls are only permitted on interior portion of site. and may not be
greater then 50% of pond perimeter.
Stormwater ReviewPrior to Building Permit:
Please design the stormwater pond with a minimum of 6 in of freeboard from
the top of control structure to top of bank, and demonstrate on stormwater
pond detail. **SEE PAGE 5 ON DOCUMENT.
Stormwater ReviewPrior to Building Permit:
Please design the stormwater pond with a minimum 6 in of clearance from
the bottom of the pond to the seasonal high water table, and provide a detail
to show the pond cross section. **SEE PAGE 5 ON DOCUMENT.
Stormwater ReviewPrior to Building Permit:
Please provide reasonable assurance that exiting storm pipes used for outfall
are in adequate condition and properly sized. **SEE PAGE 5 ON
DOCUMENT.
Stormwater ReviewGeneral Comments
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the Citys Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp **SEE PAGE 5 ON DOCUMENT.
Stormwater ReviewPrior to Building Permit:
Please provide a control structure detail. **SEE PAGE 5 ON DOCUMENT.
Stormwater ReviewPrior to Building Permit:
Please resubmit drainage calculations which show that out-parcel impervious
amount has not been exceeded with new submittal. **SEE PAGE 5 ON
DOCUMENT.
Stormwater ReviewPrior to Development Order:
Retaining walls are only permitted on interior portion of site. and may not be
greater then 50% of pond perimeter. **SEE PAGE 5 ON DOCUMENT.
Traffic Engineering Prior to a building permit:
Review
There is a potential conflict point for the inbound traffic off of US Hwy 19 N
frontage road and the south bound on site traffic circulation. Please provide a
stop sign and stop bar for the south bound onsite traffic circulation. **SEE
PAGE5 ON DOCUMENT.
Traffic Engineering Prior to CDB:
Review
Please provide 50' driveway length for the eastern driveway along
Countryside Boulevard to minimize potential conflict points for the inbound
traffic off of Countryside Boulevard and the multiple (N,S,E &W) bound on
site traffic circulation. **SEE PAGE 5 ON DOCUMENT.
Traffic Engineering Prior to a building permit:
Review
Please install wheel stops in all parking stalls abutting the retail building's
sidewalk. **SEE PAGE 5 ON DOCUMENT.
6/2/201635DRC_ActionAgenda
Traffic Engineering Prior to CDB:
Review
Please provide a turning template for a scaled fuel tanker entering, staging
and exiting the site in a forward direction without hitting any objects. **SEE
PAGE5 ON DOCUMENT.
Traffic Engineering Prior to a building permit:
Review
Show20' x 20' sight visibility triangles at all driveway connections. There
shall be no objects in the sight triangle which do not meet the City's
acceptable vertical height criteria at a level between 30 inches above grade
and eight feet above grade.
(City's Community Development Code, Section 3-904). **SEE PAGE 6 ON
DOCUMENT.
Traffic Engineering General Note(s):
ReviewApplicant shall comply with the current Multimodal Impact Fee Ordinance
and fee schedule which shall be paid prior to a Certificate of Occupancy.
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 5 ON DOCUMENT.
6/2/201636DRC_ActionAgenda
1:30 PM
Case number:FLD2016-05013 -- 667 BAY ESPLANADE
Owner(s):Clearwater Bay Club Llc
1281 Court St
Clearwater, FL 33756580
PHONE: No phone, Fax: No fax, Email: No email
Applicant:Robin Gage
300 S. Belcher Rd.
Clearwater, FL 33765
PHONE: (727)531-8517, Fax: (727)446-8036, Email:
Robin@northsideengineering.Net
Representative:Robin Gage
Northside Engineering Inc.
300 S. Belcher Rd.
Clearwater, FL 33765
PHONE: (727)531-8517, Fax: (727)446-8036, Email:
Robin@northsideengineering.Net
Location:667 Bay Esplanade: located on the east side of Bay Esplanade approximately 385
east from the Poinsettia Avenue and Bay Esplanade intersection.
Atlas Page:258A
Zoning District:Tourist
Request:The Community Development Board is reviewing a proposed 14 unit overnight
accommodation in the Tourist (T) District for the property located at 667 Bay
Esplanade. The project is 58 feet in height (from BFE), includes 17 off-street
parking spaces and requests allowable flexibility from lot width and setback
requirements, the Design Guidelines of Beach by Design, and a two-year
Development Order (Sections 2-803.D and 4-407).
Proposed Use:Overnight Accomodations
Neighborhood
Association(s):
Clearwater Beach Association
Clearwater Neighborhood Coalition
Presenter:Kevin Nurnberger, Senior Planner
6/2/201637DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Determination of Complete05/10/2016Nurnberger
Completeness
Solid Waste Review Comments05/12/2016Pryor
Please provide measurements of trash chute room and trash staging areas. Keep in mind dumpster is 7
feet from sleeve to sleeve and 4 feet from front to back. Room will need to be around 10' X 6' with the
same for staging.
Engineering Review Comments05/16/2016Simpson
Environmental Review Comments05/20/2016Kessler
Traffic Eng Review Comments05/20/2016Elbo
Parks and Rec Review Comments05/20/2016Reid
Planning Review Comments05/24/2016Nurnberger
Stormwater Review Comments05/25/2016Bawany
Land Resource Review Comments05/26/2016Crandall
Harbor Master Review No Comments05/27/2016Nurnberger
Art Review No Comments05/27/2016Nurnberger
Fire Review Comments05/30/2016Schultz
The DRC reviewed this application with the following comments:
Engineering ReviewPrior to Building Permit:
Note: the building department typically requires an 18 foot setback from a
seawall. Please provide reasonable assurance from a Licensed Professional
Engineer that the new seawall will be designed to support the proposed site
layout. **SEE PAGE 73 ON DOCUMENT.
6/2/201638DRC_ActionAgenda
Engineering ReviewGeneral Conditions:
If the proposed project necessitates infrastructure modifications to satisfy the
site-specific water capacity and pressure requirements and/or wastewater
capacity requirements, the modifications shall be completed by the applicant
and at their expense. If underground water mains and hydrants are to be
installed, the installation shall be completed and in service prior to
construction in accordance with Fire Department requirements.
Sheet C3.1 and C5.1 were reviewed for General Engineering criteria. The
additional details provided in the plan set may have been necessary for other
departmental reviews. Further comments will be forthcoming upon submittal
of a Flexible Development and/or Building Permit Application.
DRC review is a prerequisite for Building Permit review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 73 ON DOCUMENT.
Engineering ReviewPrior to Building Permit:
As per City of Clearwater Reclaimed Water System Ordinances, 32.351, and
32.376, use of potable water for irrigation is prohibited; the irrigation system
shall be hooked up to the reclaimed water system that is available to this site.
**SEE PAGE 75 ON DOCUMENT.
Engineering ReviewPrior to Building Permit:
Please provide the following notes to the demolition plan:
- All utilities shall be cut and capped prior to demolition. The Wastewater
Supervisor shall be notified.
- All existing utilities shall be protected during demolition.
- Demolition shall not cause any service interruptions for other utility
customers.
- Water meters, double-detector checks and backflow preventers are owned
by the City of Clearwater. The City shall remove and retain these items.
**SEE PAGE 73 ON DOCUMENT.
Environmental ReviewGeneral Notes:
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Offsite discharge of produced groundwater from dewatering shall comply with
dewatering guidelines from Florida Department of Environmental Protection
(FDEP), F.A.C. 62-621.300(2).
Additional permits from State agencies, such as the Southwest Florida Water
Management District or Florida Department of Environmental Protection, may
be required. Approval does not relieve the applicant from the requirements to
obtain all other required permits and authorizations. **SEE PAGE 0 ON
DOCUMENT.
Environmental ReviewPrior to issuance of building permit: Continue to provide erosion control
measures on plans. **SEE PAGE 72 ON DOCUMENT.
Fire ReviewFire Department Connection shall be a minimum of 15' from building and
shall have a supporting fire hydrant within toPlease provide details
and show on plans. **SEE PAGE 75 ON DOCUMENT.
6/2/201639DRC_ActionAgenda
Fire ReviewPlans show the fire hydrant coming off the fire line. All fire hydrants
SHALL
come off the city water main. Please provide details and show on plans.
**SEE PAGE 75 ON DOCUMENT.
Fire ReviewStandpipe connection for dock area must be connected to firepump/wet
standpipe system. Please Acknowledge. **SEE PAGE 75 ON
DOCUMENT.
Fire ReviewShall meet the requirements of NFPA 1 2012 edition chapter 16 sections
16.3.4.5 Stairs and 16.3.5 Standpipes, respectively. Please acknowledge.
**SEE PAGE 75 ON DOCUMENT.
Fire ReviewFire department access roads shall be provided
such that any portion of the facility or any portion of an exterior
wall of the first story of the building is located not more
than450 ft (46 m) from fire department access roads as measured
by an approved route around the exterior of the building
or facility. South west portion of property appears to be obstructed by
landscaping. Please provide details and show on plans. **SEE PAGE 76
ON DOCUMENT.
Land Resource ReviewThe erosion control plan must show a construction entrance prior to building
permit. **SEE PAGE 72 ON DOCUMENT.
Land Resource ReviewDRC review is a prerequisite for Building Permit Review, prior to issuance of
a building permit any and all performance based erosion and sedimentation
control measures must be approved by Environmental and or Stormwater
Engineering, be installed properly, and inspected. **SEE PAGE 76 ON
DOCUMENT.
Land Resource ReviewLand Resource Review
The erosion control plan must show a construction entrance prior to building
permit.
Land Resource ReviewLand Resource Review
DRC review is a prerequisite for Building Permit Review, prior to issuance of
a building permit any and all performance based erosion and sedimentation
control measures must be approved by Environmental and or Stormwater
Engineering, be installed properly, and inspected.
Parks and Recreation Clarify the type of the 5 units previously on property. The application and site
Reviewdata table lists as dwelling units, but the general criteria paperwork refers to
them as overnight units. Specify previous usage as hotel/motel or residential
dwellings. **SEE PAGE 70 ON DOCUMENT.
Planning ReviewClarify the trash/dumpster will be stored in the trash rooms at all times except
for collection day when it shall be wheeled out to the staging area. It will also
be returned to the trash room after collection on the same day as collection.
The trash staging area will not be fenced or walled. **SEE PAGE 73 ON
DOCUMENT.
Planning ReviewThe sidewalk along the rear property line needs to be changed from 5 feet
wide to a width no greater than 42 inches. If greater than 42 inches it is
considered a structure and must meet the rear setback of 10 feet or request
a reduction to the rear setback to 5 feet using the same method as discussed
in narrative - Sheet C3.1. **SEE PAGE 73 ON DOCUMENT.
6/2/201640DRC_ActionAgenda
Planning ReviewShow the scale on all building elevation sheets - A1.1 and A1.2. **SEE
PAGE 78 ON DOCUMENT.
Planning ReviewOn the west building elevation, on the left side it shows a building height of
65 feet from BFE where on the right side it shows an overall building height
of 69.4 feet from grade. Based on the right side the building is 58 feet from
BFE. Clarify the height and correct all applicable sheets. **SEE PAGE 78
ON DOCUMENT.
Planning ReviewThe site plan shows the parking level on the south side to be mostly open
however the south building elevation shows the parking to be mostly walled.
Clarify. **SEE PAGE 73 ON DOCUMENT.
Planning ReviewSince I do not see solid wall along the parking on south side add some mess
screening from bottom of building to ground. This will increase the
architecture detail percentage on the south facade from 53 percent to?
**SEE PAGE 73 ON DOCUMENT.
Planning ReviewOn north building elevation, add some exterior window treatments to
windows in center of building shown on levels 1,2, and 3 to increase the
architectural details percentage. **SEE PAGE 79 ON DOCUMENT.
Planning ReviewOn south building elevation, add some exterior window treatments to
windows in center of building shown on levels 1,2,3 and 4 to increase the
architectural details percentage. **SEE PAGE 79 ON DOCUMENT.
Solid Waste ReviewPlease provide measurements of trash chute room and trash staging areas.
Keep in mind dumpster is 7 feet from sleeve to sleeve and 4 feet from front
to back. Room will need to be around 10' X 6' with the same for staging.
Stormwater ReviewGeneral Comments
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the Citys Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp **SEE PAGE 74 ON DOCUMENT.
Stormwater ReviewPrior to building permit
Areas directly outfalling into tidal saltwater basins will be reviewed for water
quality impacts only. **SEE PAGE 74 ON DOCUMENT.
Stormwater ReviewPrior to building permit
Provide control structure detail. **SEE PAGE 74 ON DOCUMENT.
Stormwater ReviewPrior to Building Permit
Please provide a cross-section of stormwater vault **SEE PAGE 74 ON
DOCUMENT.
Stormwater ReviewPrior to Building Permit
Please submit drainage report including water quality and quantity
calculations for site as well as soils information including seasonal high water
table associated with stormwater management system. **SEE PAGE 74
ON DOCUMENT.
6/2/201641DRC_ActionAgenda
Stormwater ReviewStormwater Review
Prior to building permit
Areas directly outfalling into tidal saltwater basins will be reviewed for water
quality impacts
only.
Stormwater ReviewStormwater Review
General Comments
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the Citys Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp
Stormwater ReviewStormwater Review
Prior to building permit
Provide control structure detail.
Stormwater ReviewStormwater Review
Prior to Building Permit
Please provide a cross-section of stormwater vault
Stormwater ReviewStormwater Review
Prior to Building Permit
Please submit drainage report including water quality and quantity
calculations for site as well as soils information including seasonal high water
table associated with stormwater management system.
Traffic Engineering General Note(s):
Review
Applicant shall comply with the current Multimodal Impact Fee Ordinance
and fee schedule which shall be paid prior to a Certificate of Occupancy
(C.O.). The MIF amount for the new hotel is $14,436.00.
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 62 ON DOCUMENT.
Traffic Engineering Prior to a CDB:
Review
The minimum clear height throughout the garage shall be seven feet zero
inches and shall be eight feet two inches for van-accessible parking spaces
including ingress, egress and drive aisles to these spaces.
Lighting levels in parking garages having public access shall meet or exceed
the current minimum Illuminating Engineering Society (IES) standards.
All electrical conduits, pipes, downspouts, columns or other features that
could be subject to impact from vehicular traffic shall be protected from
impact damage with pipe guards or similar measures. Measures used for
protection shall not encroach into any parking space. **SEE PAGE 73 ON
DOCUMENT.
6/2/201642DRC_ActionAgenda
1:50 PM
Case number:FLS2016-05021 -- 3018 PATRICK PL
Owner(s):Leah B Beck
3018 Patrick Pl
Clearwater, FL 33759143
PHONE: No phone, Fax: No fax, Email: No email
Applicant:Leah Beck
3018 Patrick Pl.
Clearwater, FL 33759
PHONE: (727)742-4252, Fax: No fax, Email: Leahbouchard@yahoo.Com
Representative:Leah Beck
3018 Patrick Pl.
Clearwater, FL 33759
PHONE: (727)742-4252, Fax: No fax, Email: Leahbouchard@yahoo.Com
Location:3018 Patrick Place; located on the north side of Patrick place approximately 70 feet
west from where Stevens Street turns into Patrick Place.
Atlas Page:245A
Zoning District:Low Density Residential
Request:The Development Review Committee (DRC) is reviewing a proposed pool, pool
deck, and pool enclosure in the Low Density Residential (LDR) District for the
property located at 3018 Patrick Place. The project is 15 feet in height, and
requests allowable flexibility from setback requirements (Sections 2-103.B).
Proposed Use:
Detached Dwelling
Neighborhood
Association(s):
Clearwater Neighborhood Coalition
Presenter:Kevin Nurnberger, Senior Planner
6/2/201643DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Determination of Complete05/04/2016Nurnberger
Completeness
Planning Review Comments05/10/2016Nurnberger
Fire Review
No Review Required05/10/2016Nurnberger
Harbor Master Review No Review Required05/10/2016Nurnberger
Art Review
No Review Required05/10/2016Nurnberger
Solid Waste Review No Comments05/12/2016Pryor
Traffic Eng Review
No Comments05/12/2016Elbo
Parks and Rec Review No Comments05/17/2016Reid
Engineering Review
Comments05/20/2016Gluski
Environmental Review Comments05/20/2016Kessler
Land Resource Review
Comments05/25/2016Anderson
Stormwater Review Comments05/25/2016Bawany
Route to Meeting
Ready for DRC05/27/2016Nurnberger
The DRC reviewed this application with the following comments:
6/2/201644DRC_ActionAgenda
Engineering ReviewPrior to Building Permit (BCP):
Per the plat, a 10 ft. drainage easement is located along the rear of the
property line and 5 ft. utility easement located along the western property
line. Under no circumstances shall any structure(s) be constructed within the
10 ft. drainage easement and 5 ft. utility easement. The City of Clearwater
has utilities located within the 5 ft. utility easement.
Please show on the site plan / survey the location of the pool equipment,
pool heater, pool accessories, and the piping for the pool.
Under no circumstances shall the swimming pool, deck, pool equipment, and
pool heater, pool accessories, and the piping for the pool be constructed
within the easement(s).
Contractor shall be responsible for an easement inspection by the Building
Department prior to concrete pour of deck. Contractor should call at the
time of steel inspection for shell and deck. To schedule an inspection,
please call the Building Department's 24-Hour Call in Inspection Line at 727-
562-4580. The type of inspection will be a \[006\] easement inspection.
Contractor must call in an Easement Inspection \[006\] at the same time the
pool steel inspection \[502\] is called in. Contractor shall locate all property
corners and have easement line staked prior to \[006\] Easement Inspection.
General Note:
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 4 ON DOCUMENT.
Environmental ReviewGeneral Notes:
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Offsite discharge of produced groundwater from dewatering shall comply with
dewatering guidelines from Florida Department of Environmental Protection
(FDEP), F.A.C. 62-621.300(2).
Additional permits from State agencies, such as the Southwest Florida Water
Management District or Florida Department of Environmental Protection, may
be required. Approval does not relieve the applicant from the requirements to
obtain all other required permits and authorizations. **SEE PAGE 0 ON
DOCUMENT.
Land Resource ReviewPrior to Building Permit:
1. The 24 inch Laurel Oak tree located on the North East corner of the house
must be root pruned and barricade along the edge of the proposed paver
patio. The construction route needs to be changed to the opposite side of the
house to avoid impacts to the trees root system. **SEE PAGE 4 ON
DOCUMENT.
6/2/201645DRC_ActionAgenda
Land Resource ReviewPrior to issuance of a Building permit:
1. The 29 inch Laurel Oak and the 12 inch Laurel Oak need to be removed
for the construction of this swimming pool. The 29 inch Laurel Oak has
severe decay and should be removed due to the potential for failure. Please
apply for a tree removal permit at the time of Building Permit. **SEE PAGE
4 ON DOCUMENT.
Land Resource ReviewPrior to Certificate of Occupancy:
1. Two code sized native shade trees or equivalents must be planted to
replace the two that must be removed for the construction of the swimming
pool. **SEE PAGE 4 ON DOCUMENT.
Land Resource ReviewLand Resource Review
Prior to issuance of a Building permit:
1. The 29 inch Laurel Oak and the 12 inch Laurel Oak need to be removed
for the construction of this swimming pool. The 29 inch Laurel Oak has
severe decay and should be removed due to the potential for failure. Please
apply for a tree removal permit at the time of Building Permit.
Land Resource ReviewLand Resource Review
Prior to Certificate of Occupancy:
1. Two code sized native shade trees or equivalents must be planted to
replace the two that must be removed for the construction of the swimming
pool.
Planning Reviewprovide an elevation showing the pool will be at grade or 12 inches or less in
height. **SEE PAGE 4 ON DOCUMENT.
Planning ReviewProvide the height of pool enclosure. Accessory structure are permitted a
maximum height of 15 feet to flat roof line or to mid-point of pitched roof.
**SEE PAGE 4 ON DOCUMENT.
Planning ReviewIf the height of the pool enclosure exceeds 15 feet you will need to add to the
request the proposed increase in height. Residential properties may request
up to a maximum height of 20 feet for accessory structures. You will need to
provide responses for an increase in height and establish that the height is
consistent with the character of the neighborhood. **SEE PAGE 4 ON
DOCUMENT.
Planning ReviewPlanning Review
Prior to Building Permit:
1. The 24 inch Laurel Oak tree located on the North East corner of the house
must be root pruned and barricade along the edge of the proposed paver
patio. The construction route needs to be changed to the opposite side of the
house to avoid impacts to the trees root system.
Stormwater ReviewPrior to Development Order:
Pavers or structures are not permitted to be placed in the 10 foot drainage
easement to the rear of the property. Please acknowledge. **SEE PAGE 3
ON DOCUMENT.
Stormwater ReviewPrior to Building Permit:
Please design stormwater roof drains (if any) to be directed towards the
street or in accordance with lot drainage. **SEE PAGE 3 ON DOCUMENT.
6/2/201646DRC_ActionAgenda
Stormwater ReviewPrior to Building Permit:
Please provide reasonable assurance that new construction will not
adversely impact adjacent properties. **SEE PAGE 3 ON DOCUMENT.
Stormwater ReviewGeneral Comments:
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the City's Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp **SEE PAGE 3 ON DOCUMENT.
Stormwater ReviewStormwater Review
Prior to Development Order:
Pavers or structures are not permitted to be placed in the 10 foot drainage
easement to the rear of the property. Please acknowledge.
Stormwater ReviewStormwater Review
Prior to Building Permit:
Please design stormwater roof drains (if any) to be directed towards the
street or in accordance with lot drainage.
Stormwater ReviewStormwater Review
Prior to Building Permit:
Please provide reasonable assurance that new construction will not
adversely impact adjacent properties.
Stormwater ReviewStormwater Review
General Comments:
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the Citys Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp
6/2/201647DRC_ActionAgenda
2:10 PM
Case number:FLS2016-05022 -- 1317 Murray
Owner(s):
PHONE: No phone, Fax: No fax, Email: No email
Applicant:Grant Corrigan
1317 Murray Ave.
Clearwater, FL 33755
PHONE: (727)282-9607, Fax: No fax, Email: Grant.Corrigan@gmail.Com
Representative:Grant Corrigan
1317 Murray Ave.
Clearwater, FL 33755
PHONE: (727)282-9607, Fax: No fax, Email: Grant.Corrigan@gmail.Com
Location:1317 Murray Avenue: located on the east side of Murray Avenue approximately
129 feet form the Sherwood Street and Murray Avenue intersection.
Atlas Page:270B
Zoning District:Low Medium Density Residential
Request:The Development Review Committee (DRC) is reviewing a proposed pool
enclosure in the Low medium Density Residential (LMDR) District for the property
located at 1317 Murray Avenue. The project is 15 feet in height, and requests
allowable flexibility from setback requirements (Sections 2-203.C).
Proposed Use:
Detached Dwelling
Neighborhood
Association(s):
Clearwater Neighborhood Coalition
Presenter:Kevin Nurnberger, Senior Planner
6/2/201648DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Determination of Complete05/04/2016Nurnberger
Completeness
Planning Review Comments05/10/2016Nurnberger
Fire Review
No Review Required05/10/2016Nurnberger
Harbor Master Review No Review Required05/10/2016Nurnberger
Art Review
No Review Required05/10/2016Nurnberger
Solid Waste Review No Comments05/12/2016Pryor
Traffic Eng Review
No Comments05/12/2016Elbo
Parks and Rec Review No Comments05/17/2016Reid
Engineering Review
Comments05/20/2016Gluski
Environmental Review Comments05/20/2016Kessler
Stormwater Review
Comments05/25/2016Bawany
Land Resource Review No Comments05/26/2016Crandall
Route to Meeting
Ready for DRC05/27/2016Nurnberger
The DRC reviewed this application with the following comments:
6/2/201649DRC_ActionAgenda
Engineering ReviewPrior to the issuance of a Development Order (D.O.):
Per the plat, a 7.5 ft. utility easement is located along the rear of the property
line. Under no circumstances shall any structure(s) be constructed within the
7.5 ft. utility easement. The City of Clearwater has utilities located within this
area.
It appears the pool and pool deck is encroaching within the 7.5 foot utility
easement. Under no circumstances shall the swimming pool, deck, pool
equipment, and pool heater, pool accessories, piping, and the pool enclosure
be constructed within this easement.
Contractor shall be responsible for an easement inspection by Building
Department prior to installation of pool screen enclosure. To schedule an
inspection, please call the Building Department's 24-Hour Call in Inspection
Line at 727-562-4580. The type of inspection will be a "006" (easement
inspection). Contractor shall locate all property corners and have easement
line staked prior to \[006\] Easement Inspection
General Note:
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application. **SEE PAGE 7 ON DOCUMENT.
Environmental ReviewGeneral Notes:
DRC review is a prerequisite for Building Permit Review; additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Offsite discharge of produced groundwater from dewatering shall comply with
dewatering guidelines from Florida Department of Environmental Protection
(FDEP), F.A.C. 62-621.300(2).
Additional permits from State agencies, such as the Southwest Florida Water
Management District or Florida Department of Environmental Protection, may
be required. Approval does not relieve the applicant from the requirements to
obtain all other required permits and authorizations. **SEE PAGE 0 ON
DOCUMENT.
Planning ReviewYou will need to provide an updated survey. According to Pinellas County
property Appraiser website and Google earth there appears to be pavement
and an accessory structure in the rear yard north of the pool. I do not see an
approved building construction permit for the structures. One structure looks
as if in rear yard setback. The structures are not shown on the survey. need
to verify if structures are on property. If so they will be required to be added
to the current request. Also need to verify if structures do exist to determine
if when they were added to the property the any additional impervious
surface area does not exceed the ,maximum ISR of 0.65. **SEE PAGE 3
ON DOCUMENT.
6/2/201650DRC_ActionAgenda
Planning Reviewprovide the height of the proposed pool enclosure either from grade to flat
roof line or from grade to mid point of a pitched roof. **SEE PAGE 3 ON
DOCUMENT.
Planning ReviewPlease provide the addresses of the properties whose accessory structures
are shown in submitted pictures. **SEE PAGE 4 ON DOCUMENT.
Planning ReviewYou need to show the location of the enclosure - will it be directly over the
pool or over the entire pool deck. Mark on plan footprint of pool enclosure as
well as an elevation of it's height. Max height is 15 feet. **SEE PAGE 3
ON DOCUMENT.
Stormwater ReviewPrior to Building Permit:
Please design stormwater roof drains (if any) to be directed towards the
street or in accordance with lot drainage. **SEE PAGE 7 ON DOCUMENT.
Stormwater ReviewPrior to Building Permit:
Please provide reasonable assurance that new construction will not
adversely impact adjacent properties. **SEE PAGE 7 ON DOCUMENT.
Stormwater ReviewGeneral Comments:
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the Citys Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp **SEE PAGE 7 ON DOCUMENT.
Stormwater ReviewStormwater Review
Prior to Building Permit:
Please design stormwater roof drains (if any) to be directed towards the
street or in accordance with lot drainage.
Stormwater ReviewStormwater Review
Prior to Building Permit:
Please provide reasonable assurance that new construction will not
adversely impact adjacent properties.
Stormwater ReviewStormwater Review
General Comments:
DRC review is a prerequisite for Building Permit Review. Additional
comments may be forthcoming upon submittal of a Building Permit
Application.
Please refer to the Citys Storm Drainage Design Criteria as found at the City
website:
http://www.myclearwater.com/gov/depts/pwa/engin/StormwaterMgt/StormDra
inageDesignCriteria.asp
6/2/201651DRC_ActionAgenda
4:00 PM
Case number:ANX2016-05017 -- 1608 LEVERN ST
Owner(s):Daniel L Barrett
1608 Levern St
Clearwater, FL 33755
PHONE: (727)642-5430, Fax: No fax, Email: No email
Applicant:Daniel Barrett
1608 Levern St
Clearwater, FL 33755
PHONE: (727)642-5430, Fax: No fax, Email: No email
Location:0.215 acres located on the north side of Levern Street approximately 95 feet west
of Ridge Avenue.
Atlas Page:270B
Zoning District:Low Medium Density Residential
Request:This case involves a request for voluntary annexation into the City of Clearwater. It
is proposed that the property be assigned a Future Land Use Map designation of
Residential Low (RL) and an initial zoning category of Low Medium Density
Residential (LMDR).
Proposed Use:Detached Dwelling
Neighborhood
Association(s):
Clearwater Neighborhood Coalition
Presenter:
Kyle Brotherton, Planner
6/2/201652DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Determination of Complete05/03/2016Brotherton
Completeness
Planning Review No Comments05/03/2016Brotherton
Engineering Review
Comments05/11/2016Simpson
Traffic Eng Review No Comments05/12/2016Elbo
Solid Waste Review
No Comments05/12/2016Pryor
Parks and Rec Review No Comments05/20/2016Reid
Environmental Review
No Comments05/20/2016Kessler
Stormwater Review Comments05/25/2016Bawany
Land Resource Review
No Comments05/26/2016Crandall
Fire Review No Comments05/30/2016Schultz
The DRC reviewed this application with the following comments:
Engineering ReviewGeneral Comments:
Annexation into the City of Clearwater will generate monthly stormwater
utility fees on your City Utility bill. In contrast, properties in Unincorporated
Pinellas County are typically assessed a yearly stormwater utility fee as part
of the property tax bill.
Please note, any changes to the site and/or building shall require bringing all
sub-standard sidewalks and sidewalk ramps adjacent to or a part of the
project up to standard, including A.D.A. standards (truncated domes per
FDOT Index #304).
6/2/201653DRC_ActionAgenda
4:00 PM
Case number:ANX2016-05018 -- 2138 BELL CHEER DR
Owner(s):Thompson, Rory
2192 Bell Cheer Dr
Clearwater, FL 33764-4846
PHONE: No phone, Fax: No fax, Email: No email
Applicant:
2138 Bell Cheer Dr
Clearwater, FL 33764-4846
PHONE: (727)678-2737, Fax: No fax, Email: No email
Location:0.824 acres located generally south of Druid Road, east of South Hercules Avenue,
north of Lakeview Road, and west of South Belcher Road.
Atlas Page:308B
Zoning District:
Request:This case involves requests for voluntary annexation into the City of Clearwater. It
is proposed that the properties be assigned an initial Future Land Use Map
designation of Residential Low (RL) and an initial zoning category of Low Medium
Density Residential (LMDR). The properties are: 2112, 2138 and 2196/2198 Bell
Cheer Drive.
Proposed Use:Detached Dwelling
Neighborhood
Association(s):
Clearwater Neighborhood Coalition
Presenter:Kyle Brotherton, Planner
6/2/201654DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Determination of Complete05/03/2016Brotherton
Completeness
Planning Review No Comments05/03/2016Brotherton
Engineering Review
Comments05/11/2016Simpson
Traffic Eng Review No Comments05/12/2016Elbo
Solid Waste Review
No Comments05/12/2016Pryor
Parks and Rec Review No Comments05/20/2016Reid
Environmental Review
No Comments05/20/2016Kessler
Stormwater Review No Comments05/25/2016Simpson
Land Resource Review
No Comments05/26/2016Crandall
Fire Review No Comments05/30/2016Schultz
The DRC reviewed this application with the following comments:
Engineering ReviewGeneral Comments:
Annexation into the City of Clearwater will generate monthly stormwater
utility fees on your City Utility bill. In contrast, properties in Unincorporated
Pinellas County are typically assessed a yearly stormwater utility fee as part
of the property tax bill.
Please note, any changes to the site and/or building shall require bringing all
sub-standard sidewalks and sidewalk ramps adjacent to or a part of the
project up to standard, including A.D.A. standards (truncated domes per
FDOT Index #304).
6/2/201655DRC_ActionAgenda
4:00 PM
Case number:ATA2016-05007 -- 2160 BELL CHEER DR
Owner(s):Andrea Bloomfield
2160 Bell Cheer Dr
Clearwater, FL 33764-4846
PHONE: (727)461-5262, Fax: No fax, Email: No email
Applicant:Andrea Bloomfield
2160 Bell Cheer Drive
Clearwater, FL 33764-4846
PHONE: (727)461-5262, Fax: No fax, Email: No email
Representative:Andrea Bloomfield
2160 Bell Cheer Drive
Clearwater, FL 33764-4846
PHONE: (727)461-5262, Fax: No fax, Email: No email
Location:0.236 acres located on the north side of Bell Cheer Drive, approximately 470 feet
west of South Belcher Road.
Atlas Page:308B
Zoning District:Low Medium Density Residential
Request:This case involves a City initiated annexation of a single parcel (previously signed
ATA) into the City of Clearwater. It is proposed that the property be assigned an
initial Future Land Use Map designation of Residential Low (RL) and an initial
zoning category of Low Medium Density Residential (LMDR).
Proposed Use:
Detached Dwelling
Neighborhood
Association(s):
Clearwater Neighborhood Coalition
Presenter:Katie See, Senior Planner
6/2/201656DRC_ActionAgenda
Workflow:
Review NameTask StatusStatus DateLast Name
Engineering Review Comments05/12/2016Simpson
Traffic Eng Review
No Comments05/12/2016Elbo
Determination of Complete05/12/2016See
Completeness
Planning Review No Comments05/20/2016See
Environmental Review
No Comments05/20/2016Kessler
Parks and Rec Review No Comments05/20/2016Reid
Stormwater Review
No Comments05/24/2016Bawany
Land Resource Review No Comments05/26/2016Crandall
Fire Review
No Comments05/30/2016Schultz
The DRC reviewed this application with the following comments:
Engineering ReviewGeneral Comments:
Annexation into the City of Clearwater will generate monthly stormwater
utility fees on your City Utility bill. In contrast, properties in Unincorporated
Pinellas County are typically assessed a yearly stormwater utility fee as part
of the property tax bill.
Please note, any changes to the site and/or building shall require bringing all
sub-standard sidewalks and sidewalk ramps adjacent to or a part of the
project up to standard, including A.D.A. standards (truncated domes per
FDOT Index #304).
6/2/201657DRC_ActionAgenda