PERMIT C52-1092 FOR 3363 LF 8"VCP 2557 LF 6"VCP FOR 150 SINGLE FAMILY HOMES
I
I
6~
~.
'--~.
State of Florida
DEPARTMENT OF ENVIRONMENTAL REGULATION
APPROVAL OF INSTALLATION AND USE OF A
SEWAGE COLLECTION/TRANSMISSION SYSTEM
April 28, 1977
Pinellas County - DW
Mr. Thomas T. Chesnut
Northwood Estates
2650 Landmark Drive
Clearwater, Florida 33519
FOR AGENCY USE ONLY
Dear Mr. Chesnut:
Approval No.:
Issued:
Expires:
Treatment
Facility:
C52-l092
April 28. 1977
February 15, 1978
Clearwater Northeast
In reference to your recent application to this department for approval of the installation of a sewage
collection/transmission. system to serve the following project:
Project Name:
Project Location;
Northwood Estates Tract ifF"
Landmark Drive and Eastland Bl~~.
Project Description:
150 single family homes
360.population
Flow: 36,000 GPD
Approval of construction only has been granted subject to the following conditions:
1. The design, installation and use of the facilities shall be in accordance with: your applica-
tion dated April 5. 1977 ; the Water Pollution Control Federation
"Manual of Practice No.9"; appropriate provisions of Chapters 403 and 471, Florida
Statutes; and the rules and regulations of the Department of Environmental Regulation.
2. The approval is only for INSTALLATION of a WAstewater collection/transmission system
and does not relate to any water supply aspects. The engineer of record shall supervise
the construction of the engineering features of the system. At the end of construction,
but prior to use, the "Certification/Approval to Use" statement (found on Page 2) must
be completed and submitted tot his department and a copy forwarded to the local pro-
gram (if applicable) of your county.
3. This approval is based on the understanding that adequate reserve capacity, as stated in
your application and certified by the trreatment plant owner, will be available at the
Clearwa ter Nor theas t sewerage treatment plant so that
the wastewaters generated by this project will be collected, treated and disposed of in ~_____
compliance with Chapter 403, Florida Statutes and the rules and regulations of thi~ ~
department. /~
-~
4. Individual connections that will increase flow to the sewage treatmenV~arenot in-
cluded in this approval./~
----
--
------------
'.rm PERM 11.9 (Feb 77) Page 1 of 2
---~--'-')
..~rI 1",...1
, :
I
I
5. Before starting construction of this project, approvals from other federal, state, or local
departments/agencies may be required.
6. Construction shall commence prior to
7. Where water and sewer mains cross with less than eighteen inehes (18") vertical
clearance, the sewer will be twenty feet (20' - 0") of eitherc.ast iron pipe or concrete
encased vitrified clay pipe, centered on the point of crossing.
8. When a water main parallels a sewer main, a separation of at least ten feet (10' - 0")
should be maintained where practical.
Sincerely,
~;uc~ -
frirerim Di~~rict Manager
Southwest District
CERTIFICATION/APPROVAL TO USE
This is to certify that, with the exception of the deviations noted in the attached letter dated
, the installation of this system has been completed and tested in accordance
with the application and approved plans. The system, if properly maintained and operated, shall comply
with the W.P.C.F. "Manual of Practice Number 9", Chapters 471 and 473, Florida Statutes, and the rules
and regulations of the Department of Environmental Regulation. The initial three months of operation
shall be under my engineering supervision.
PROJECT ENGINEER CERTIFICATION
DER APPROVAL TO USE
Signature
Date
Signature of District Manager
Date
Florida Registration Number
(Affix Seal)
------~-
.-....
cc:
Owner of Tre~~nt Plant
Project Engineer ~
~-------
Local Program ___-....
~-
Picot B. Floyd V
S. Lloveras
Tampa Bay Regional Planning Council
-1 ~tda Public Service Commission
Centrd.l. L.l.J..co
~--
000071 V
OER Form PERM 11-9 (Feb 77) Page 2 of 2 _------------