NEW PRESURE MAINS FOR IMPROVED DISTRBUTION AND FIRE PROTECTION
!
,^,
)
t..
This Space For Use By Approving District
STATE OF FLORIDA
DEPARTMENT OF ENVIRONMENTAL REGULATION
APPLICATION FOR PERMIT TO CONSTRUCT/ALTER
DRINKING WATER PLANT SYSTEM
Thll 811111:" Fur lllll 8y AlIl'lClVillU nlllrlc:l
Approval Date
ID.~-~
Permit No. SZ7.!!> - 2~03 - k
OEA Forn.l'lflM 1;) 2 (Dee, 77) PIli" 1014
r?\ DO;) S 00 - 01
.
#
~.. . J
1
l
Date August 13,. ] 979
To: THE DEPARTMENT OF ENVIRONMENTAL REGULATION
The City of Clearwater, rlorida
(Insert title of body making application, i.a, municipality, corporation or Individual)
whose address is
P.O. Box 4748, Clearwater. Florida
(Street end Number)
3351R
(City)
authorized by law to act for the said
City of Clearwater
(Insert city, town or corporation)
and to expend its funds for water supply and treatment works, herewith submit for consideration the plans and specifications
and other necessary data (including DER Form PERM 13-2A) prepared by
Briley, Wild & Associates. Inc.
(Engineer or firm)
of
P.O. Box 607, Ormond Beach, Florida 32074
(Address)
who is hereby authorized to represent the applicant in the engineering features including supervision of construction and appro,
priate certification as to compliance with the approved plans and specifications of the project for the installation of
Southwest Service Area Phase 2 - New pressure mains f~r improved distribution and
fi re protect ion. (Clearly describe new system, new plant, modification, extension)
to serve _ Southwest Service Area located at Clearwater, Florida
(Subdlvlson, plant, school, other) (Location)
in/near the city of C 1 earwa t e r in the county of Pine 11 as 0 , State
of Florida, as required by the regulations of the Department and herewith make application to the Department for the approval
of this project.
These plans, specifications and related documents will be approved and accepted by
when they have received the approval of the Department.
the City Commission
(Board, Council, Diractors, Etc.)
Upon construction, these facilities will be owned by
City of Clearwater
and will be
operated and maintained by
City Forces
(City forces, name of utility, co., or owner)
whose address is
same as above
(Street and Number)
(City or Town)
This application is made under and in full accord with the provisions of Chapter 403, the Florida Safe Drinking Water Act, Sections
403.850,,864, Florida Statutes. THE APPLICANTS AGREE THAT NO CHANGES IN OR DEVIATION FROM THE PLANS
AND SPECIFICATIONS APPROVED BY THE DEPARTMENT WILL BE MADE EXCEPT WITH THE CONSENT AND APPROV-
AL OF THE DEPARTMENT. FURTHER, THE APPLICANTS AGREE TO THE SPECIFIC REQUIREMENTS RELATIVE TO
OPERATION AND OPERATIONAL FUNDS THAT ARE MADE A PART OF THIS APPLICATION. (See Proviso No.2, Page 4).
Is this application associated with or part of a Development of Regional Impact (DR!) pursuant to Chapter 380, Florida Statutes,
and Chapter 22F-2, Florida Administrative Code? _ Yes -X- No
REMARKS:
Area to be im roved is in a Ion
a
Richard B. Gassett. P.E. Fla. #21421
Typed Neme and Fla. Registration No.
~TY, ped, nRme 'and. Title 0,' 8boye
, L .
..t!~ .. ~
- ..
Signature: City Clerk, Board Secretary. Etc.
AFFIX
ENGINEER'S
SEAL
DEA Form PE RM 13.2 (Dec. 77) Page 2 of 4
I ature: Appr and Correctness
Thomas A. Bustin, City Attorney
Typed Name and Tltle:-All8"t- foto -ope,..tlen- end- M..IA18__
.
.
....._,ll:
I
1
INFORMATION REGARDING PROPOSED PUBLIC WATER WORKS
Submit comprehensive engineering report with all plans and specifications, and compLete such portions of this form as relate to
the treatment plant. (Use supplemental sheets if necessary.)
Name of WatlH System Supplying Water~___---0-n_-2.fJ:;Jearwater
Previous approval Permit Number(s)
5274 - 2903
725,000
Treatment $
-0-
Distribution $
-0-
Est. Cost this Project: Supply $
Storage: Ground
gal. Elev.
MGD, Treatment
4.3 mg
Total $ 725,000
18.7
MGD
EXISTING SUPPLY AND TREATMENT FACILITIES:
Supply
18.7
20 mg
gal: Pressure Tank
-0-
gal.
Service Pumping .
13.000
gpm
Capacity of emergency pumping units: Well
-0-
gpm. service
9.500
gpm
Utility is Capable of Supplying
36,000
Equivalent Residential Connections.
Max. Daily output
14,4
MG.
July, 1979
date
Equivalent Residential Connections 34285
420 gpd
PROPOSED IMPROVEMENT OR DISTRIBUTION EXTENSION
n/a
Plant increase
-0-
MGD
Supply:
Pressure Tank
n/a
Chlorinator
Elve. Storage
n/a
n/a
Plant: Aerator
n/a
Gnd. Storage
n/a
n/a
Service pumping
gpm
Aux. Power for
n/a
Present Population (municipality. institution, etc.)
120,000 (service area)
Estimated population to be connected: 5 years
n/a
n/a
Equivalent to
n/a
residential services.
Additional Population (served by this project)
10 years
n/a
20 years
n/a
Present per capita consumption
120 gpd
Per capita estimated future
130 gpd
Give any industrial users or abnormal demands
none
Interconnection with other system
.n/ ~.____ .._._
cross connections _,.___.TJi_~____...
Min, sile pipu
6"
HllSiduUllllllssuru 81 puuk load . .30.ps t ._. ____Is filII control provided? yes
Describe dead-end conditions and necessity for flushing all dead ends have provis ions (fire hygrC!-!!ts_'_d__
shut off valves, blow offs) for routing flushing.
6" - 7408 LF, 8" - 28,431 LF
List lengths of new pipe lines 6" and larger .
Remarks To improve water distribution and fire protection
DE R Form PE HM 132 (Oac. 71) Pago 3 of 4
"
~
.-
1
I
PROVISOS
The plans for the proposed improvements cited in the foregoing application are hereby approved under authority of Chapter
403, the Florida Safe Drinking Water Act, Sections 403.850-.864, Florida Statutes with the following provisions:
1. Construction of this project must be commenced within one year from the date of this application; otherwise plans and
specifications must be resubmitted for approval by this Department. The engineer of record in this application is responsible
for supervision of the construction of this project and upon completion shall inspect for complete conformity to the plans and
sper.ificatiom liS upproved, A roport of such Inspection In writing and .Igned by the englnoar .hall be rendllred to thl! inturll5lltd
Coul1ty HUlIllh ()llplIllmnnlllnd In 11111 ()"p/lrtlll/tnl of Envlronmol1l/tlllnlllllllllon.
:.1. This Ilpplllvnl Is glvon with tho undOlstamJing thot upon the In8lallation 01 such wOlks, its oplllations shall hI! "I (lend lHltlr.r
the Care of a competent person, whose qualifications are approved by the Department and the operation shall be carried out accord-
ing to best accepted practice and in accordance with the requirements of the rules and regulations of the Department. This includes
not only the provision of continuing essential funds for operation and maintenance of chemical supplies for plant operation: But
also the funds for maintenance equipment and supplying the needs of a suitable water plant laboratory which is required for proper
operation of this water treatment facility.
3. Water supply facilities including mains shall be installed, cleaned, disinfected, and bacteriologically cleared for service, in accor-
dance with the latest applicable AWWA Standards and Department rules and regulations.
4. Where water and sewer mains cross with less than 18" vertical clearance, the sewer will be 20' of either cast iron pipe or con-
crete encased vitrified clay pipe, centered on the point of crossing. When a water main parallels a sewer main, a separation of
at least 10' should be maintained where practical.
The official copies of plans and specifications accompanying this application have been sealed and stamped with the permit
number as indicated hereon. Only such plans and specifications arc included in this approval and any erasures, additions or altera-
tions affecting the efficiency of operation or public health protective value of the proposed improvements will make such approval
null and void.
District Manager
By:
DER Form PERM 13.2 (Dec. 77) Page 4 of 4